Skip to main content
Schneider Electric A9P54716

Schneider A9P54716 Acti9 iC40N MCB, 16 A C-Curve 3P+N 10 kA

MPN A9P54716
Active

Schneider Electric Acti9 iC40N miniature circuit breaker, A9P54716, 16 A rated current, C-curve, 3P+N, 10 kA Icu at 400 V AC, dual-rated EN/IEC 60898-1 and 60947-2.

$112.00 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9P54716 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage400 V AC 50/60 Hz
Insulation voltage ui440 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity10 kA Icu at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-2

All specifications

A9P54716 additional specifications
ParameterValue
ColorWhite
Depth74 mm
Width54 mm
Height85 mm
Electrical life cycles20000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric A9P54716 is a 16 A C-curve miniature circuit breaker from the Acti9 iC40N series, configured as 3P+N. It carries a dual rating to EN/IEC 60898-1 (6 kA Icn at 400 V AC) and EN/IEC 60947-2 (10 kA Icu at 400 V AC), which means it can be specified for either domestic-distribution or industrial-panel applications where the higher breaking capacity is needed for fault coordination. The thermal-magnetic trip unit provides C-curve protection (magnetic trip at 5–10× In per 60898-1, 8× In ±20% per 60947-2), suited for mixed resistive and moderate inductive loads like lighting circuits, small motor starters, and general-purpose branch protection.

Breaking capacity and dual-standard rating

The 6 kA Icn under EN/IEC 60898-1 is the domestic/commercial rating, sufficient for most final distribution circuits. Having both on one nameplate means the same part can be stocked for both job types, simplifying BOM management for an integrator who works across residential and light-industrial sites.

Clip-on mounting to DIN rail (35 mm symmetrical rail per EN 60715) with a 54 mm width (6 x 9 mm pitches). The 3P+N configuration places the neutral pole on the left, with the toggle control providing ON/OFF and trip-indicator local signalling. Tunnel-type terminals accept 1–16 mm² rigid or 1–10 mm² flexible conductors; tightening torque is 2 N·m.

Quality labels include OVE, IMQ, and AENOR. Earth-leakage protection requires a separate Vigi block — not integrated.

MPN