Skip to main content
Schneider Electric A9P64610

Schneider Electric A9P64610 Acti9 iC40N MCB, D Curve, 10 A,

MPN A9P64610
Active

Schneider Electric Acti9 iC40N miniature circuit breaker, A9P64610, 1P+N, D curve, 10 A rated current, 10 kA breaking capacity per IEC 60947-2.

$79.33 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9P64610 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage230 V AC 50/60 Hz
Insulation voltage ui400 V AC 50/60 Hz conforming to EN/IEC 60947-2
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite

All specifications

A9P64610 additional specifications
ParameterValue
Depth74 mm
Width18 mm
Height85 mm
Electrical life cycles20000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

D-curve MCB for motor and transformer branch circuits

The Schneider Electric A9P64610 is an Acti9 iC40N miniature circuit breaker rated 10 A with a D tripping curve, configured as 1P+N. The D curve's magnetic trip threshold of 10 to 14 times In means it tolerates the inrush current of small motors, transformers, and solenoid loads without nuisance tripping — the 10 A rating handles steady-state draw, while the high short-time magnetic pickup passes the starting surge. Breaking capacity is 10 kA Icu at 230 V AC per IEC 60947-2, and 6 kA Icn per IEC 60898-1. The 6 kA rating applies under the domestic-standard 60898-1 test sequence; for panel design, use the 60947-2 value. This is a thermal-magnetic breaker with suitability for isolation per IEC 60947-2, meaning it provides a visible break and meets the touch-safe gap requirements for a disconnecting means. The ON/OFF and trip indicator on the toggle give local status without needing a voltmeter.

Tunnel terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible copper; strip length 14 mm, tightening torque 2 N·m. The IP20 finger-safe terminals suit enclosed panels; the modular enclosure is rated IP40 when installed in a cabinet. Padlocking provision allows lockout/tagout on the toggle. Ambient conditions: 95% relative humidity at 55 °C, operating altitude up to 2000 m, pollution degree 3 per IEC 60947-2 (conductive pollution or dry non-conductive that becomes conductive from condensation — typical for industrial control panels).

MPN
A9P64610