Skip to main content
Schneider Electric A9TDEC616

Schneider Electric A9TDEC616 Acti9 iCV40N ARC, 16 A, Curve B

MPN A9TDEC616
Active

Schneider Electric Acti9 Active iCV40N ARC, arc-fault detection device, 1P+N, 16 A, curve B, 6 kA Icn / 10 kA Icu at 230 V AC, clip-on DIN rail, white (RAL 9003).

$359.91 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9TDEC616 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Voltage230 V AC 50 Hz
Insulation voltage ui250 V AC 50 Hz between phase and neutral
Breaking capacity6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 61009-2-1 10 kA Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max50 °C
Temp operating min-25 °C
Storage temperature-40...80 °C
Pollution degree2 conforming to EN/IEC 62606

All specifications

A9TDEC616 additional specifications
ParameterValue
ColorWhite (RAL 9003)
Depth73 mm
Width36 mm
Height91 mm
Electrical life cycles20000 cycles 230 V AC 50 Hz
Mechanical life cycles20000 cycles
AccuracyVoltage: +/- 2 % Current: +/- 2 % Power: +/- 5 %
Operating temperature-25...50 °C

Product details

Rated 16 A with a B curve, it breaks up to 6 kA Icn (service) and 10 kA Icu (ultimate) at 230 V AC, 50 Hz — enough to clear a bolted fault on a residential or light-commercial final subcircuit without upstream coordination issues.

The 16 A rated current and B curve mean the device trips magnetically between 3 and 5 times In (48–80 A) — standard for resistive and general-purpose loads like lighting, socket outlets, and small appliances. The 1P+N configuration switches the line and monitors the neutral; the neutral is left, which matches the standard Acti9 busbar layout. The 6 kA Icn (EN/IEC 61009-2-1) is the service breaking capacity for an RCBO-type device; the 10 kA Icu (EN/IEC 60947-2) is the ultimate breaking capacity under the industrial standard, giving headroom for higher fault-current locations. The thermal-magnetic trip unit handles overloads (thermal) and short-circuits (magnetic). The arc-fault detection (AFDD) adds series and parallel arc detection per EN/IEC 62606, which is what distinguishes this from a standard RCBO — it catches glowing connections and carbonised insulation faults that a thermal-magnetic element alone might miss.

The toggle control gives local ON/OFF switching plus a fault-trip LED and arc-fault diagnostic indicator.

MPN
A9TDEC616