Skip to main content
Schneider Electric A9TPED610

Schneider Electric A9TPED610 Acti9 iC40N ARC, 10 A, 1P+N, C-

MPN A9TPED610
Active

Schneider Electric Acti9 Active ARC iC40N, arc-fault detection circuit breaker, A9TPED610, 1P+N, 10 A, C-curve, 6 kA Icn at 230 V AC.

$353.05 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9TPED610 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Voltage230 V AC 50 Hz
Insulation voltage ui250 V AC
Breaking capacity3000 A Icn1 at 230 V AC 50 Hz conforming to EN/IEC 60898-1 10 kA Icu at 230 V AC 50 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 60898-1
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max40 °C
Temp operating min-25 °C
Storage temperature-40...80 °C
Pollution degree2

All specifications

A9TPED610 additional specifications
ParameterValue
ColorWhite (RAL 9003)
Depth73 mm
Width36 mm
Height91 mm
Electrical life cycles20000 cycles
Mechanical life cycles20000 cycles
AccuracyVoltage: +/- 2 % Current: +/- 2 % Power: +/- 5 %
Operating temperature-25...40 °C

Product details

Arc-fault MCB for final subcircuits

It combines overcurrent protection (thermal-magnetic, C-curve, 10 A rated) with series arc-fault detection per EN/IEC 62606, in a 1P+N (single-pole switched neutral) format. The 6 kA Icn at 230 V AC (EN/IEC 60898-1) and 10 kA Icu (EN/IEC 60947-2) cover the fault-clearing demands of residential and light-commercial final subcircuits.

The 6 kA Icn is the service breaking capacity under IEC 60898-1 — adequate for domestic panels with a typical upstream fault level below 6 kA. The 10 kA Icu (IEC 60947-2) is the ultimate breaking capacity for industrial backplanes where higher fault current is possible; the part can interrupt a 10 kA fault once and must then be replaced. Limitation class 3 means it lets through very little let-through energy (I²t) on a short-circuit, protecting downstream wiring and loads.

Clip-on mounting to DIN rail (EN 60715). Width is 36 mm (4 x 9 mm pitches). Tunnel terminals accept 1–16 mm² rigid or 1–10 mm² flexible cable; strip length 14 mm, tighten to 2 N·m. Cable entry top and bottom. Neutral position left. IP20 finger-safe terminals. Tropicalisation severity B per IEC 60068-2-30 for 28 days — suitable for humid environments without condensation.

Arc-fault detection and diagnostics

Local signalling: ON/OFF toggle position plus a fault-trip LED and arc-fault diagnostic indicator. Event management covers overvoltage, earth leakage, overload, and series arc faults. Electrical data recording logs date/time and maintenance indicators — useful for post-fault analysis. Measurement accuracy: voltage ±2%, current ±2%, power ±5%.

MPN
A9TPED610