Skip to main content
Schneider Electric A9TYB4240

Schneider Electric A9TYB4240 Acti9 VigiARC iC60, 40A 30mA AF

MPN A9TYB4240
Active

Schneider Electric Acti9 VigiARC iC60 arc fault detection with residual current protection add-on block, 2P, 40 A, 30 mA, 230 V AC, DIN rail clip-on, IP20.

$329.99 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9TYB4240 specifications
ParameterValue
Voltage230 V AC
Insulation voltage ui250 V AC
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max40 °C
Temp operating min-25 °C
Storage temperature-40...80 °C
Pollution degree2
ColorWhite (RAL 9003)
Depth73 mm
Width54 mm
Height91 mm
Electrical life cycles10000 cycles > 25 A 20000 cycles <= 25 A
Mechanical life cycles20000 cycles
Operating temperature-25...40 °C

Product details

It combines two protection functions in one DIN-rail module: 40 A overcurrent protection and 30 mA earth leakage, plus series arc-fault detection. Rated for 230 V AC, 50 Hz networks, 2 poles, neutral left.

The 40 A rated current ([In]) sets the continuous load capacity — sized for a final subcircuit feeding lighting, socket outlets, or small equipment up to that ampacity. The 30 mA earth-leakage sensitivity is the standard threshold for personal protection against indirect contact in residential and commercial final circuits. The residual current trip is instantaneous and voltage-independent, meaning it operates regardless of supply voltage — a reliability advantage over electronic RCDs that need line power to trip. The arc-fault detection meets EN/IEC 62606, the standard for AFDDs. It monitors the waveform for the high-frequency signature of a series arc (a loose connection or damaged conductor) and trips before the arc can start a fire. The device also complies with EN/IEC 61009-1 and 61009-2-1 for RCBOs. Pollution degree 2 covers normal indoor environments with non-conductive contamination.

Clip-on mounting to a standard DIN rail. The module occupies 2 x 9 mm pitches — 18 mm total width. Neutral is on the left.

Tropicalisation severity B per IEC 60068-2-30 for 28 days — handles high-humidity climates. IMQ quality label marks it for the Italian market. Maximum operating altitude 2000 m. Electrical durability: 10,000 cycles above 25 A, 20,000 cycles at or below 25 A. Mechanical durability: 20,000 cycles.

Current-production part — no end-of-life notice on record. Sourced through independent distribution channels. Submit an RFQ for current pricing and lead time; availability confirmed at quote time.

MPN
A9TYB4240