Schneider Electric A9TYB4625 Acti9 VigiARC iC40, 25 A, 30 mA

MPN A9TYB4625
Active

Schneider Electric Acti9 VigiARC iC40, arc fault detection device with residual current protection (AFDD+RCBO), 1P+N, 25 A, 30 mA, Type A-SI, 230 V AC, DIN rail clip-on.

$323.68 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9TYB4625 specifications
ParameterValue
Voltage230 V AC
Insulation voltage ui250 V AC
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max40 °C
Temp operating min-25 °C
Storage temperature-40...80 °C
Pollution degree2
ColorWhite (RAL 9003)
Depth73 mm
Width36 mm
Height91 mm
Electrical life cycles10000 cycles > 25 A 20000 cycles <= 25 A
Mechanical life cycles20000 cycles
Operating temperature-25...40 °C

Product details

The Schneider Electric A9TYB4625 Acti9 VigiARC iC40 is a combined arc fault detection device (AFDD) and residual current circuit breaker with overcurrent protection (RCBO) in a single 36 mm wide, 1P+N module. It is rated at 25 A and 30 mA earth-leakage sensitivity, per the datasheet. The Type A-SI (Super Immunised) residual current protection is voltage-independent, meaning it trips on leakage current alone without needing a separate power supply for the detection circuit. This matters for panel builders: the SI classification handles pulsed DC and high-frequency AC leakage from modern switched-mode loads without nuisance tripping.

Clip-on mounting to DIN rail, 2 module pitches (36 mm wide). Neutral on the left. Tunnel terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible cable; strip length 14 mm, tightening torque 2 N·m.

Environmental and durability

Operating temperature range -25 to 40 °C; storage -40 to 80 °C. Electrical durability: 10,000 cycles above 25 A, 20,000 cycles at or below 25 A. Mechanical durability 20,000 cycles. Local signalling includes ON/OFF/fault trip LED and arc fault diagnostic indicator. Records date and time of fault events with maintenance indicators.

MPN