Skip to main content
Schneider Electric A9Z22240

Schneider Electric A9Z22240 Acti9 iID RCCB, 40 A, 100 mA, 2P

MPN A9Z22240
Active

Schneider Electric Acti9 iID, A9Z22240, Residual Current Circuit Breaker (RCCB), 2P, 40 A, 100 mA, Type A, 10 kA.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9Z22240 specifications
ParameterValue
Control typeToggle
Voltage220...240 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3
ColorWhite
Depth73 mm
Width36 mm
Height91 mm
Electrical life cyclesAC-1: 15000 cycles
Mechanical life cycles20000 cycles
Operating temperature-25...60 °C

Product details

Rated 40 A continuous on a 220...240 V AC 50/60 Hz network, it trips on 100 mA residual current, Type A, covering sinusoidal AC and pulsating DC fault currents up to that threshold. That 100 mA sensitivity is a common spec for general distribution circuits where a lower 30 mA threshold isn't required by code — think submain feeders or lighting panels where nuisance tripping on leakage from long cable runs would be a problem.

Clip-on DIN rail mount, 4 module pitches wide (36 mm per pitch, so 144 mm total width). Neutral on the left, toggle control, IP20 on the body with IP40 inside a modular enclosure. That's enough for a 40 A feed conductor without a separate terminal block.

Current-production part per the manufacturer's lifecycle stage. The A9Z22240 is an active catalog item in the Acti9 range — no last-time-buy window, no successor to track. For a BOM freeze, this is a stable SKU with no imminent obsolescence risk.

Breaking and making capacity (Idm/Im) is 1500 A, which covers the typical prospective fault current at the device terminals in a subdistribution panel. Electrical durability is 15,000 cycles under AC-1 (resistive load), mechanical durability 20,000 cycles — that's a solid service life for a panel that sees regular switching. Impulse withstand voltage (Uimp) is 6 kV, insulation voltage (Ui) 500 V AC, so it's comfortable in 400 V three-phase panels even though the operational coil voltage is 240 V line-to-neutral. The 8/20 µs impulse withstand of 250 A means it survives surge events without nuisance tripping.

That's the compliance basis for CE marking in the EU and UKCA in Great Britain. The Type A classification covers sinusoidal AC and pulsating DC residual currents, which is the minimum requirement for most general-purpose and EV-charging circuits under IEC 60364.

MPN
A9Z22240