Skip to main content
Schneider Electric ATV1200A4706060

Schneider ATV1200A4706060 Altivar 1200 MV Drive, 470 kVA

MPN ATV1200A4706060
Active

Schneider Electric Altivar 1200 series, ATV1200A4706060 medium voltage variable speed drive, 470 kVA apparent power, 393 kW motor power, 2970-3630 V supply, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV1200A4706060 specifications
ParameterValue
Input type30 pulse diode rectifier bridge
Protection typeGround fault protection: drive
Coil voltage220 V
Current65 A
IP ratingIP41 / IP42 / IP31
Temp storage max60 °C
Temp storage min-10 °C
Temp operating max50 °C
Temp operating min0 °C
Storage temperature-10...60 °C
Pollution degreePollution degree 2
Depth1400 mm (standard efficiency) 1500 mm (high efficiency)
Width2860 mm (standard efficiency) 3160 mm (high efficiency)
Height2590 mm standard efficiency 2740 mm high efficiency
Operating positionVertical +/- 10 degree
Operating temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)

Product details

Floor-standing MV drive, 470 kVA, for synchronous or asynchronous motors

The ATV1200A4706060 is a medium voltage drive from the Altivar 1200 series, delivering 470 kVA apparent power and rated for 393 kW motor output on synchronous or asynchronous machines. Supply voltage range is 2970 to 3630 V, fed through a 30-pulse diode rectifier bridge that keeps line harmonics low enough to meet EN/IEC 61800-3 without external filtering. The drive is assembled in a floor-standing enclosure with separate air flows for power and control sections, and includes an integrated EMC filter.

Physical footprint and cooling demand

Standard efficiency configuration measures 1400 mm deep, 2860 mm wide, and 2590 mm tall; the high-efficiency variant adds 100 mm to depth, 300 mm to width, and 150 mm to height. Cooling is forced convection requiring 16,600 m³/h airflow for standard efficiency and 19,900 m³/h for high efficiency — the fan supply is 380 V AC internal, with an optional external supply. Noise level at full cooling is 80 dB, so ear protection is expected near the enclosure during operation.

Overload profile and protection

Standard overload rating handles 1.2× rated current for 60 seconds and 1.5× for 3 seconds; the high overload profile extends to 1.5× for 60 seconds and 1.85× for 3 seconds. Ground fault protection is built into the drive, and dielectric strength between earth and power terminals is tested at 20 kV AC. The prospective short-circuit current rating is 31.5 kA for 150 ms, giving selectivity headroom in medium voltage distribution.

CE marked and designed to EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1 standards. The drive composition includes a phase-shifting transformer, medium voltage arrestors, cooling fans, HMI, and 15 power cells — all housed in a grey RAL 7032 enclosure.

I/O and control interface

Four software-configurable analogue inputs accept 0-20 mA or 4-20 mA signals at 24 V max with 250 Ohm impedance; two analogue outputs mirror the same current ranges. Six discrete inputs are standard, expandable to ten; control supply is 220 V AC at 3 kVA, with an optional 220 V AC/DC external supply. Electrical connection uses M10 screw-type bars accepting up to 6 × 40 mm² cable, with entry from the top or bottom of the enclosure.

MPN