Skip to main content
Schneider Electric ATV1200A56504242

Schneider ATV1200A56504242 MV Drive, 4723 kW, 5650 kVA

MPN ATV1200A56504242
Active

Schneider Electric Altivar 1200 ATV1200A56504242 medium-voltage AC drive, 4723 kW / 5650 kVA, 24-pulse diode rectifier, 2970–3630 V input, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV1200A56504242 specifications
ParameterValue
Input type24 pulse diode rectifier bridge
Protection typeGround fault protection: drive
Coil voltage220 V
Current850 A
IP ratingIP42 / IP31 / IP41
Temp storage max60 °C
Temp storage min-10 °C
Temp operating max50 °C
Temp operating min0 °C
Storage temperature-10...60 °C
Pollution degreePollution degree 2
Depth1800 mm (standard efficiency)
Width6670 mm (standard efficiency)
Height2740 mm standard efficiency
Operating positionVertical +/- 10 degree
Operating temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)

Product details

Medium-voltage drive, not a 480 V VFD

The ATV1200A56504242: This is a medium-voltage drive with supply voltage limits of 2970 to 3630 V — it is not a standard 480 V VFD. Rated motor power is 4723 kW with an apparent power of 5650 kVA, placing it squarely in large MV drive territory for high-horsepower synchronous or asynchronous motors. The input stage uses a 24-pulse diode rectifier bridge, which inherently cancels the 5th and 7th harmonics without an active front end. This makes it suitable for sites with strict harmonic limits (IEEE 519) where a multi-pulse transformer is already part of the installation.

Physical footprint and cooling

The drive ships in a floor-standing enclosure with separate air flows for power and control sections. Dimensions are 6670 mm wide by 2740 mm high by 1800 mm deep (standard efficiency variant) — this requires a dedicated equipment room with adequate floor space and overhead clearance for cable entry from the bottom or top. Cooling is forced convection, moving 70,000 m³/h of air. The noise level is 80 dB — hearing protection is necessary in the drive room during operation.

Overload capability and fault withstand

The drive offers two overload profiles: standard overload handles 1.2× In for 60 seconds and 1.5× In for 3 seconds; high overload handles 1.5× In for 60 seconds and 1.85× In for 3 seconds. This covers both normal starting duty and high-torque applications like crushers or mills. Prospective line short-circuit current withstand is 31.5 kA for 150 ms — this sets the SCCR for upstream protection coordination. Ground fault protection is integrated into the drive.

The drive is CE marked and complies with EN/IEC 60204-11 (machinery safety), EN/IEC 60529 (enclosure protection), EN/IEC 61800-3 (EMC for adjustable-speed drives), EN/IEC 61800-4 (general requirements), and EN/IEC 61800-5-1 (electrical safety). Electrical isolation between power and control is provided. Dielectric strength is 20 kV AC between earth and power terminals.

MPN
ATV1200A56504242