Skip to main content
Schneider Electric ATV1200A6603333

Schneider Electric ATV1200A6603333 AC Drive (VFD) 480V

MPN ATV1200A6603333
Active

Schneider Electric Altivar 1200 ATV1200A6603333 medium-voltage AC drive, 552 kW, 660 kVA, 18-pulse diode rectifier, 2970...3630 V supply, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV1200A6603333 specifications
ParameterValue
Input type18 pulse diode rectifier bridge
Protection typeGround fault protection: drive
Coil voltage220 V
Current135 A
IP ratingIP42 / IP41 / IP31
Temp storage max60 °C
Temp storage min-10 °C
Temp operating max50 °C
Temp operating min0 °C
Storage temperature-10...60 °C
Pollution degreePollution degree 2
Depth1400 mm (standard efficiency) 1500 mm (high efficiency)
Width2760 mm (standard efficiency) 3060 mm (high efficiency)
Height2520 mm standard efficiency 2670 mm high efficiency
Operating positionVertical +/- 10 degree
Operating temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)

Product details

What this drive handles and where it fits

The ATV1200A6603333 is a medium-voltage Altivar 1200 drive rated for 552 kW motor power at 660 kVA apparent power, accepting a supply range of 2970...3630 V. It drives both synchronous and asynchronous motors — common for large pumps, fans, compressors, and conveyors in process plants, water treatment, and mining. The 18-pulse diode rectifier bridge on the input side draws 135 A line current and keeps harmonic distortion low enough to meet IEEE 519 without external filters in most installations. Integrated EMC filter is standard.

Overload profile and fault handling

Standard overload rating holds 1.2× In for 60 s and 1.5× In for 3 s; high overload pushes to 1.5× In for 60 s and 1.85× In for 3 s. This gives headroom for starting high-inertia loads or clearing transient overloads without tripping. The drive withstands a prospective line short-circuit current of 31.5 kA for 150 ms — enough to coordinate with upstream MV switchgear on most distribution networks. Ground-fault protection is built into the drive.

Cooling, enclosure, and installation constraints

The drive ships in a floor-standing enclosure with separate airflows for the transformer and power cells. Forced convection cooling moves 9900 m³/h (standard efficiency) or 13 200 m³/h (high efficiency). Noise level is 80 dB — plan for hearing protection if the drive is in a manned area. Dimensions: 2760 mm wide (3060 mm high-efficiency), 2520 mm tall (2670 mm high-efficiency), 1400 mm deep (1500 mm high-efficiency). Pollution degree 2 per EN/IEC 61800-5-1.

Auxiliary supplies and control wiring

The control electronics require an external 220 V AC supply at 3 kVA; the cooling fan runs on 380 V AC internal supply. Optional external supplies for both are available. Electrical isolation between power and control circuits is standard. Six discrete inputs (10 optional) and four software-configurable analogue inputs (0...20 mA / 4...20 mA, 250 Ω impedance) handle most process signals. One analogue output (same current range) is provided. Dielectric strength between earth and power terminals is 10 kV AC.

MPN
ATV1200A6603333