Skip to main content
Schneider Electric ATV212HD75N4LCD

Schneider ATV212HD75N4LCD AC Drive, 75 kW, 100 hp, 480 V

MPN ATV212HD75N4LCD
Obsolete

Schneider Electric Altivar 212 ATV212HD75N4LCD AC drive, 75 kW / 100 hp, 480 V, 320 x 630 x 290 mm, IP20, with integrated EMC filter.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV212HD75N4LCD specifications
ParameterValue
Connector type1 open style 1 RJ45
Main product or component typeVariable speed drive
Voltage= 1 mOhm 500 V DC for 1 minute
Current141.8 A at 380 V 111.3 A at 480 V
Horsepower100 hp
Frequency50...60 Hz - 5...5 %
Temp storage max70 °C
Temp storage min-25 °C
Temp operating max50 °C
Temp operating min-10 °C
Storage temperature-25...70 °C
Pollution degree3 conforming to IEC 61800-5-1
Depth290 mm
Width320 mm
Height630 mm
Operating positionVertical +/- 10 degree

Product details

75 kW at 480 V — motor power and line-side draw

The ATV212HD75N4LCD is a 75 kW / 100 hp Altivar 212 AC drive for asynchronous motors, rated for a 380–480 V supply. Line current at 480 V is 111.3 A; at 380 V it draws 141.8 A, with an apparent power of 105.3 kVA at the lower voltage. This is the drive for a 100 hp pump, fan, or conveyor — the Altivar 212 series is positioned as a mid-functionality, cost-optimised VFD for building services and light industrial duty.

Panel fit — 320 x 630 x 290 mm with 666 m³/h airflow

The drive measures 320 mm wide, 630 mm high, and 290 mm deep — a substantial footprint that demands a back-panel or floor-standing enclosure. The integrated fan moves 666 m³/h of air through the heatsink, so the enclosure must allow free intake and exhaust; the operating position is vertical ±10°. Altitude derating applies above 1000 m: 1 % per 100 m up to 3000 m, with a 2000 m limit for corner-grounded distribution networks.

Protection coverage and compliance envelope

The drive includes integrated Class C2 EMC filtering and meets EN/IEC 61800-3 environments 1 and 2 categories C1 through C3, plus EN 55011 Class A Group 1. Protection covers input phase loss, DC bus overvoltage/undervoltage, motor phase break, short-circuit between motor phases, overcurrent to earth, and PTC probe monitoring.

For a 100 hp VFD that is still in mature production, the supply posture is straightforward: submit an RFQ with your quantity and target delivery window.