Skip to main content
Schneider Electric ATV6000C288A6666ND

Schneider ATV6000C288A6666ND AC Drive 480V, 2300 kW

MPN ATV6000C288A6666ND
Active

Schneider Electric Altivar Process ATV6000, AC Drive (VFD) 480V, 3-phase, 2300 kW normal duty / 2140 kW heavy duty, 30-pulse diode rectifier, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV6000C288A6666ND specifications
ParameterValue
Input type30 pulse diode rectifier bridge
Display type10 inch LCD touch screen multi-language
Connector type2 RJ45 on the control block)Ethernet IP/Modbus TCP 1 RJ45 on the control block)Modbus serial
Current234 A heavy duty 252 A normal duty
Frequency50 Hz +/- 5 %
Phases3-phase
IP ratingIP31
Temp storage max50 °C
Temp storage min0 °C
Temp operating max60 °C
Temp operating min1.2 °C
Storage temperature32...122 °F (0...50 °C)
Pollution degreePollution degree 2
Depth63.0 in (1600.0 mm)
Width183.5 in (4660.0 mm)
Height108.3 in (2751.0 mm)
Operating temperature32...104 °F (0...40 °C) 104...122 °F (40...50 °C) with derating factor -13...158 °F (-25...70 °C) during transport

Product details

30-pulse rectifier and harmonic compliance

The ATV6000C288A6666ND: The 30-pulse diode rectifier front end keeps input current THDI below 3% per IEEE 519-1992, so you can skip the external harmonic filter on most utility feeds. Line current draw is 234 A in heavy-duty profile, 252 A in normal duty — size the upstream transformer and cabling for the higher figure plus the transformer's own magnetizing inrush.

Motor power and duty cycling

Rated 2300 kW normal duty, 2140 kW heavy duty — the heavy-duty ceiling is the one that governs continuous process loads like pumps or compressors where the drive must ride through a 150% overload for 60 seconds. The IGBT inverter cells use multilevel PWM, which gives a cleaner output waveform and reduces motor bearing stress compared to a two-level topology.

Physical footprint and installation planning

This is a floor-standing enclosure, 108.3 inches tall, 183.5 inches wide, 63.0 inches deep. That footprint plus the 83 dB noise level and 100 kW heat rejection at normal duty means the drive needs its own room with forced ventilation or a dedicated HVAC zone — it will not share a cabinet with PLCs or low-voltage controls.

Lifecycle and procurement posture

No direct drop-in substitute exists from Schneider; the ATV6000 family is the active platform for this power class.