Schneider Electric ATV6000C288A6666ND — AC Drive (VFD) 480V

Schneider ATV6000C288A6666ND AC Drive 480V, 2300 kW

MPNATV6000C288A6666ND
Active

Schneider Electric Altivar Process ATV6000, AC Drive (VFD) 480V, 3-phase, 2300 kW normal duty / 2140 kW heavy duty, 30-pulse diode rectifier, floor-standing enclosure.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV6000C288A6666ND — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV6000
Product range / familyAltivar Process ATV6000
ATV6000C288A6666ND — Power & Output
ParameterValue
Motor power (kW)2300 kW normal duty 2140 kW heavy duty
Continuous output current224 A heavy duty 241 A normal duty
Max. transient current420 A 3 s heavy duty) 361 A 3 s normal duty)
Apparent power2880 kVA
ATV6000C288A6666ND — Input / Supply
ParameterValue
Rated supply voltage range6.6 kV +/- 10 %
Input line current234 A heavy duty 252 A normal duty
Internal/auxiliary suppliesInternal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 17 kVA
ATV6000C288A6666ND — Control & Performance
ParameterValue
Output frequency range0.1...120 Hz
Asynchronous motor control modesClosed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop
Synchronous motor control modesPermanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor
ATV6000C288A6666ND — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated IEC 61800-3 category C3 control Integrated IEC 61800-3 category C4 Power
Protection functionsLine supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overvoltages on the DC bus drive Thermal overload for transformer drive Cabinet overheating drive Overcurrent drive Overload drive Short-circuit protection drive IGBT for each cell drive Thermal protection motor Motor phase break motor Motor earth fault motor Break on the control circuit drive Fan monitoring drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)31.5 kA 150 ms
ATV6000C288A6666ND — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 conforming to IEC 60529
Acoustic noise level83 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure
ATV6000C288A6666ND — Environmental
ParameterValue
Operating ambient temperature32...104 °F (0...40 °C) 104...122 °F (40...50 °C) with derating factor -13...158 °F (-25...70 °C) during transport
Operating altitude3280.84...6561.68 ft (1000...2000 m) with derating factor
Relative humidity5...95 % without condensation IEC 60068-2-3
Storage / transport temperature32...122 °F (0...50 °C)
Pollution degree2 IEC 61800-5-1
ATV6000C288A6666ND — Approvals
ParameterValue
Certifications & markingCULus CE UKCA
Standards complianceIEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076 UL 347A
ATV6000C288A6666ND — Communication
ParameterValue
Communication protocolsEthernet IP/Modbus TCP

Product details

30-pulse rectifier and harmonic compliance

The ATV6000C288A6666ND: The 30-pulse diode rectifier front end keeps input current THDI below 3% per IEEE 519-1992, so you can skip the external harmonic filter on most utility feeds. Line current draw is 234 A in heavy-duty profile, 252 A in normal duty — size the upstream transformer and cabling for the higher figure plus the transformer's own magnetizing inrush.

Motor power and duty cycling

Rated 2300 kW normal duty, 2140 kW heavy duty — the heavy-duty ceiling is the one that governs continuous process loads like pumps or compressors where the drive must ride through a 150% overload for 60 seconds. The IGBT inverter cells use multilevel PWM, which gives a cleaner output waveform and reduces motor bearing stress compared to a two-level topology.

Physical footprint and installation planning

This is a floor-standing enclosure, 108.3 inches tall, 183.5 inches wide, 63.0 inches deep. That footprint plus the 83 dB noise level and 100 kW heat rejection at normal duty means the drive needs its own room with forced ventilation or a dedicated HVAC zone — it will not share a cabinet with PLCs or low-voltage controls.

Lifecycle and procurement posture

No direct drop-in substitute exists from Schneider; the ATV6000 family is the active platform for this power class.

Frequently asked questions

What compliance documentation does Schneider Electric provide for ATV6000C288A6666ND?

The drive carries CULus, CE, and UKCA markings. It is designed to IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, EN/IEC 60076, and UL 347A.

What is ATV6000C288A6666ND's listed depth?

The enclosure depth is 63.0 inches (1600 mm). Combined with the 183.5-inch width and 108.3-inch height, this drive requires a dedicated floor area with front and rear access for cable entry and maintenance.