Skip to main content
Schneider Electric ATV6A0C50T4

Schneider ATV6A0C50T4 Altivar Process ATV600, 500 kW

MPN ATV6A0C50T4
Active

Schneider Electric Altivar Process ATV600, ATV6A0C50T4, modular drive, 500 kW normal duty / 400 kW heavy duty at 480 V, 736 A line current (normal duty), integrated EMC filter C3, forced convection cooling, cabinet mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV6A0C50T4 specifications
ParameterValue
Main product or component typeVariable speed drive
Current736.0 A 480 V normal duty) 634.0 A 480 V heavy duty)
Horsepower700.0 hp at 480 V normal duty 600.0 hp at 480 V heavy duty
Frequency50...60 Hz - 5...5 %
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min1.1 °C
Storage temperature-40...158 °F (-40...70 °C)
Pollution degreePollution degree 2
Data format8 bits, configurable odd, even or no parity Modbus serial
Operating temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor

Product details

The ATV6A0C50T4 is a modular Altivar Process ATV600 drive, rated 500 kW at 480 V normal duty and 400 kW heavy duty, with a corresponding motor rating of 700 hp normal / 600 hp heavy. The drive ships as a kit — separate control unit, power module, mounting brackets, and a set of fuses — so your panel layout needs to account for the physical split, not a single monoblock.

Power and supply considerations

Line current at 480 V sits at 736 A normal duty, 634 A heavy duty. The integrated EMC filter meets IEC 61800-3 category C3 — that's for industrial second-environment installations; no additional external filter needed for standard industrial mains. Control power requires a separate 24 V DC supply: digital inputs accept 19–30 V, STO circuit runs on 21–27 V, and there's an internal 10.5 V DC for a reference potentiometer. The control supply is protected at <200 mA with overload and short-circuit protection built in. Plan on a dedicated 24 V DC supply sized for the full logic load, not just the STO current.

Cabinet-mount only, forced convection cooling. Pollution degree 2 per IEC 61800-5-1, which means non-conductive dust and occasional condensation — no aggressive chemical exposure expected. Shock rated to 7 gn, 11 ms. Operating humidity 5–95 % non-condensing.

Safety and compliance

Safe Torque Off (STO) with SIL 3, wired to STOA/STOB on 24 V DC supply. CE marked, compliant with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, and IEC 13849-1.