Skip to main content
Schneider Electric ATV6B0C20N6

Schneider ATV6B0C20N6 Altivar Process ATV600, 132kW ND, 110k

MPN ATV6B0C20N6
Active

Schneider Electric Altivar Process ATV600, modular VFD, ATV6B0C20N6, 132 kW ND / 110 kW HD at 500 V, integrated EMC filter C3, STO SIL 3, cabinet mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV6B0C20N6 specifications
ParameterValue
Main product or component typeVariable speed drive
Current169.0 A 500 V normal duty) 141.0 A 500 V heavy duty)
Frequency50...60 Hz - 5...5 %
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min1.1 °C
Storage temperature-40...158 °F (-40...70 °C)
Pollution degreePollution degree 2
Data format8 bits, configurable odd, even or no parity Modbus serial
Operating temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor

Product details

Drive at a glance – integrator first look

This ATV6B0C20N6 is the 132 kW normal duty / 110 kW heavy duty variant of the Altivar Process ATV600 series, rated at 500 V supply. Line current pulls 169 A in normal duty, 141 A in heavy duty. The integrated EMC filter meets IEC 61800-3 category C3 for 300 m shielded cable runs – no external filter needed in most industrial panel installations. Safe Torque Off (STO) to SIL 3 is included on the control board, which simplifies safety circuit design for machinery.

Mounting, cooling, and connections

The modular design includes Slot A for fieldbus option cards – Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen in three physical variants. Slot A/B also accepts digital/analog I/O or output relay extension modules. This means you can lock in the exact communication interface without buying a whole new drive variant.

Compliance and lifecycle – sourcing note

THDI is less than 5% at full load per IEEE 519 – the integrated EMC filter and line reactor design keeps harmonics under that threshold without extra hardware for most applications. Prospective line short-circuit current 50 kA.

Communication and control

Two-wire RS-485 Modbus serial on the control board, with RTU frame, configurable parity and 1–247 addresses. Ethernet (10/100 Mbit/s) is native for Modbus TCP with half/full duplex autonegotiation. Switching frequency adjustable 2–4.9 kHz with derating above base. Motor types: asynchronous and synchronous – the ATV600 Process line handles permanent magnet motors as well as induction. Protection list covers thermal, overcurrent, earth fault, overspeed, phase loss, DC bus overvoltage/undervoltage, and break on control circuit. The thermal model protects both motor and drive separately.

MPN
ATV6B0C20N6