Schneider ATV6B0C25Q4 Altivar Process ATV600, 250 kW at 400

MPN ATV6B0C25Q4
Active

Schneider Electric Altivar Process ATV600 modular drive, ATV6B0C25Q4, 250 kW / 400 V normal duty, 200 kW heavy duty, integrated EMC filter for 300 m cable, STO SIL3, forced convection cooling.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV6B0C25Q4 specifications
ParameterValue
Main product or component typeVariable speed drive
Current389.0 A at 400 V (normal duty) 313.0 A at 400 V (heavy duty)
Frequency50...60 Hz - 5...5 %
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min1.1 °C
Storage temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1

Product details

Drive ratings and duty

The ATV6B0C25Q4 is a modular Altivar Process ATV600 drive from Schneider, rated 250 kW at 400 V in normal duty and 200 kW in heavy duty, with a built-in EMC filter complying with IEC 61800-3 category C3 for up to 300 m shielded motor cable. Line current sits at 389 A normal duty, 313 A heavy duty at 400 V, giving you a realistic sizing number for breaker and cabling decisions — the heavy-duty figure is the one to use for pump starts with high inertia. Total harmonic current distortion is guaranteed below 5% at full load per IEEE 519, which keeps you off the utility's radar for THD penalties on larger installations.

Integrated EMC and field wiring

The built-in C3 filter handles 300 m of shielded cable without an external output reactor — that covers the typical rise main distance to a submersible pump. No extra cabinet space needed for a filter board. Line-side connection uses screw terminals; motor connection uses M10 bars. That lets you land field wiring with standard tools, no special crimps. Forced convection cooling dissipates 10170 W at normal duty and 8040 W at heavy duty, both at 2.5 kHz switching. Account for this heat in cabinet ventilation.

Safety and communication options

Safe torque off is integrated to SIL3 — that covers the functional safety requirement for a wet-well pump station without an external safety relay. It's monitored internally for motor phase break and overspeed. Dual communication slots: Slot A accepts Profibus DP, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (daisy chain RJ45, SUB-D 9, or screw terminals). Slot A/B takes digital/analog I/O or relay extension modules. That's one slot for the plant network, one for local I/O. Built-in Modbus serial (RS-485, RTU, 1…247 addresses) and Modbus TCP (10/100 Mbit) come standard. For existing water SCADA over Modbus, you don't need an extra gateway.

The drive ships as a kit: control unit, power module (160 kW basic frame), mounting hardware, a set of fuses, and front cover. The modular variant means the power section and control section are separated for easier panel layout and service swap. Compliance documentation on file covers IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and ISO 13849-1. CE marking is on the nameplate.

MPN
ATV6B0C25Q4