Skip to main content
Schneider Electric ATV6B0C31Q6

ATV6B0C31Q6 Altivar Process ATV600 Drive, 315 kW Normal Duty

MPN ATV6B0C31Q6
Active

Schneider Electric Altivar Process ATV600 series, modular version ATV6B0C31Q6, 315 kW normal duty at 690 V, 287 A line current, integrated C3 EMC filter, STO SIL3 safety.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV6B0C31Q6 specifications
ParameterValue
Main product or component typeVariable speed drive
Current287.0 A 690 V normal duty) 228.0 A 690 V heavy duty)
Frequency50...60 Hz - 5...5 %
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min1.1 °C
Storage temperature-40...158 °F (-40...70 °C)
Pollution degreePollution degree 2
Data format8 bits, configurable odd, even or no parity Modbus serial
Operating temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor

Product details

Fieldbus and safety integration

The ATV6B0C31Q6: This modular ATV6B0 variant covers synchronous and asynchronous motors up to 315 kW on a 690 V normal-duty profile, or 250 kW in heavy duty. Slot A accepts Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen via RJ45 / SUB-D 9 / screw terminals; for I/O expansion a second slot (A/B) handles relay and analog/digital extension modules. The native Modbus serial interface runs at up to 38.4 kbit/s, RTU or ASCII, with configurable parity and 1–247 node addressing. For SIL 3 applications the Safe Torque Off circuit is built into the drive — no external safety contactor required, reducing panel clutter and wiring.

Cabinet integration and mounting

Cabinet mount only — no through-panel or back-box version. Forced convection cooling (fans) requires clearances per the installation manual; the 73 dB noise level at rated load means acoustic consideration in occupied spaces. The kit includes the control unit, mechanical mounting kits, power connection set with fuses, a 200 kW power module, and front cover. Line-side connection uses M10 x 2 bars; motor side similarly M10 x 2 bars. Control wiring via removable screw terminals accepting 0.5–1.5 mm² (AWG 20–16). Prospective line Isc is 50 kA, so verify upstream SCCR. For altitudes above 1000 m derate current; up to 2000 m is acceptable with derating. Vibration resistance 1.5 mm p-p (2–13 Hz) and 0.5 gn (13–200 Hz) per IEC 60068-2-6; shock resistance 4 gn for 11 ms. The modular form factor simplifies replacement of the power section separately from the control unit.

MPN