Skip to main content
Schneider Electric ATV6B0C63T6

Schneider ATV6B0C63T6 Altivar Process 600 V VFD, 650 hp

MPN ATV6B0C63T6
Active

Schneider Electric Altivar Process ATV600 ATV6B0C63T6 AC Drive (VFD) 600V, 650 hp normal duty, 511 A line current, 531 kVA, cabinet mount, modular version.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV6B0C63T6 specifications
ParameterValue
Main product or component typeVariable speed drive
Current511.0 A 600 V normal duty) 434.0 A 600 V heavy duty)
Horsepower650.0 hp at 600 V normal duty 550.0 hp at 600 V heavy duty
Frequency50...60 Hz - 5...5 %
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min1.1 °C
Storage temperature-40...158 °F (-40...70 °C)
Pollution degreePollution degree 2
Data format8 bits, configurable odd, even or no parity Modbus serial
Operating temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor

Product details

650 hp at 600 V — normal vs heavy duty

The ATV6B0C63T6 is a 650 hp normal-duty drive at 600 V, delivering 511 A line current and 531 kVA apparent power. In heavy-duty service the numbers drop to 550 hp, 434 A, and 451 kVA — that's the margin for constant-torque loads like conveyors or extruders that need full torque at low speed.

STO SIL 3 and the safety circuit

Safe Torque Off rated SIL 3 per IEC 61508 means the drive removes motor torque without a main contactor — the safety function lives in the control board, not an external relay. For a commissioning engineer, that translates to fewer interposing safety relays in the panel and a faster certification walk-through on a machine guarding loop.

EMC filter and cable length — 300 m

Integrated EMC filter rated for 300 m of motor cable, Category C3 per IEC 61800-3. That covers most plant-floor runs without an external output choke — the filter handles conducted emissions up to the second environment (industrial). The 50 kA prospective short-circuit current rating at the line side means the drive coordinates with a 50 kA SCCR panel without an upstream current-limiting fuse.

Fieldbus slot architecture

Slot A accepts Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen — the same hardware carrier, different communication module. The drive also carries a native Modbus serial port (RS-485, 2-wire, 4.8 to 38.4 kbit/s) and a dual-port Ethernet/IP + Modbus TCP interface at 10/100 Mbit/s. For a controls integrator, the slot approach means the fieldbus decision can wait until the panel build phase, not the drive order date.

Harmonics and THDI <5 %

Total harmonic current distortion below 5 % at full load, meeting IEEE 519. That's the built-in active front-end or multi-pulse rectifier doing its work — no external line reactor or active filter needed for most utility compliance checks. At partial load the THDI stays low enough to avoid nuisance transformer heating in shared-bus installations.

Cabinet mount and UL type 1/12

Cabinet-mount design with UL Type 1 (finger-safe) and Type 12 (dust-tight) ratings when integrated into an enclosure. The forced-convection cooling (2 to 4.9 kHz switching frequency, derated above 4 kHz) needs clearance above and below the heatsink — plan for 150 mm minimum free air path. The line-side screw terminals and M10 motor bus bars take up to 500 MCM cable.

The ATV6B0C63T6 is a standard catalog part in the Altivar Process ATV600 family, so spares availability is stable for the foreseeable future. Quoted to order against your BOM; lead time and volume pricing confirmed at RFQ through authorized distribution.

MPN