Skip to main content
Schneider Electric ATV6B0C63T6 — AC Drive (VFD) 600V

Schneider ATV6B0C63T6 Altivar Process 600 V VFD, 650 hp

MPNATV6B0C63T6
Active

Schneider Electric Altivar Process ATV600 ATV6B0C63T6 AC Drive (VFD) 600V, 650 hp normal duty, 511 A line current, 531 kVA, cabinet mount, modular version.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV6B0C63T6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV600
Device short name / model codeATV6B0
Product / component typeVariable speed drive
ATV6B0C63T6 — Electrical (input)
ParameterValue
Rated supply voltage600 V - 10...10 %
Network phases3 phases
Supply frequency50...60 Hz - 5...5 %
Line (input) current511.0 A 600 V normal duty) 434.0 A 600 V heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<5 % full load IEEE 519
ATV6B0C63T6 — Output / Performance
ParameterValue
Apparent power531 kVA at 600 V normal duty 451 kVA at 600 V heavy duty
Continuous output current650.0 A at 2.5 kHz normal duty 520.0 A at 2.5 kHz heavy duty
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV6B0C63T6 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV6B0C63T6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV6B0C63T6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)< 2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level75 dB 86/188/EEC
ATV6B0C63T6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1
Agency markings / approvalsCE

Product details

650 hp at 600 V — normal vs heavy duty

The ATV6B0C63T6 is a 650 hp normal-duty drive at 600 V, delivering 511 A line current and 531 kVA apparent power. In heavy-duty service the numbers drop to 550 hp, 434 A, and 451 kVA — that's the margin for constant-torque loads like conveyors or extruders that need full torque at low speed.

STO SIL 3 and the safety circuit

Safe Torque Off rated SIL 3 per IEC 61508 means the drive removes motor torque without a main contactor — the safety function lives in the control board, not an external relay. For a commissioning engineer, that translates to fewer interposing safety relays in the panel and a faster certification walk-through on a machine guarding loop.

EMC filter and cable length — 300 m

Integrated EMC filter rated for 300 m of motor cable, Category C3 per IEC 61800-3. That covers most plant-floor runs without an external output choke — the filter handles conducted emissions up to the second environment (industrial). The 50 kA prospective short-circuit current rating at the line side means the drive coordinates with a 50 kA SCCR panel without an upstream current-limiting fuse.

Fieldbus slot architecture

Slot A accepts Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen — the same hardware carrier, different communication module. The drive also carries a native Modbus serial port (RS-485, 2-wire, 4.8 to 38.4 kbit/s) and a dual-port Ethernet/IP + Modbus TCP interface at 10/100 Mbit/s. For a controls integrator, the slot approach means the fieldbus decision can wait until the panel build phase, not the drive order date.

Harmonics and THDI <5 %

Total harmonic current distortion below 5 % at full load, meeting IEEE 519. That's the built-in active front-end or multi-pulse rectifier doing its work — no external line reactor or active filter needed for most utility compliance checks. At partial load the THDI stays low enough to avoid nuisance transformer heating in shared-bus installations.

Cabinet mount and UL type 1/12

Cabinet-mount design with UL Type 1 (finger-safe) and Type 12 (dust-tight) ratings when integrated into an enclosure. The forced-convection cooling (2 to 4.9 kHz switching frequency, derated above 4 kHz) needs clearance above and below the heatsink — plan for 150 mm minimum free air path. The line-side screw terminals and M10 motor bus bars take up to 500 MCM cable.

The ATV6B0C63T6 is a standard catalog part in the Altivar Process ATV600 family, so spares availability is stable for the foreseeable future. Quoted to order against your BOM; lead time and volume pricing confirmed at RFQ through authorized distribution.

Frequently asked questions

What is the ATV6B0C63T6 rated for in normal duty vs heavy duty?

Normal duty: 650 hp, 511 A line current, 531 kVA at 600 V. Heavy duty: 550 hp, 434 A line current, 451 kVA at 600 V. The heavy-duty rating applies to constant-torque loads where the drive must deliver full torque continuously at low speed.

Does the ATV6B0C63T6 have Safe Torque Off?

Yes, STO rated SIL 3 per IEC 61508. It removes motor torque without an external safety contactor, simplifying the safety circuit in a guarding application.

What fieldbus options fit the ATV6B0C63T6?

Slot A accepts Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen modules. The drive also has native Modbus serial and dual-port Ethernet/IP + Modbus TCP.

How long a motor cable can the ATV6B0C63T6 handle?

The integrated EMC filter is rated for 300 m of motor cable (IEC 61800-3 Category C3). Longer runs may need an external output reactor.

MPN