Skip to main content
Schneider Electric ATV6B0M10T6

Schneider ATV6B0M10T6 Altivar Process ATV600 Drive, 1000 hp

MPN ATV6B0M10T6
Active

Schneider Electric, Altivar Process ATV600 series, modular variable frequency drive, ATV6B0M10T6, 1000 hp at 600 V normal duty, 785 A line current, STO SIL 3, integrated EMC filter C3.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV6B0M10T6 specifications
ParameterValue
Main product or component typeVariable speed drive
Current785.0 A 600 V normal duty) 628.0 A 600 V heavy duty)
Horsepower1000.0 hp at 600 V normal duty 800.0 hp at 600 V heavy duty
Frequency50...60 Hz - 5...5 %
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min1.1 °C
Storage temperature-40...158 °F (-40...70 °C)
Pollution degreePollution degree 2

Product details

The Schneider ATV6B0M10T6 is a modular Altivar Process ATV600 drive rated 1000 hp at 600 V normal duty and 800 hp at 600 V heavy duty, drawing 785 A line current in normal duty and 628 A in heavy duty. It handles both synchronous and asynchronous motors, with an output voltage up to supply voltage.

The 785 A normal-duty line current sets the incoming cable and fuse sizing; the 628 A heavy-duty figure governs the same for the tougher profile. Apparent power is 815 kVA at 600 V normal duty and 652 kVA at 600 V heavy duty, which gives the transformer or generator sizing anchor. The prospective line short-circuit current rating is 50 kA, so the upstream protection must coordinate at that level. Switching frequency is adjustable from 2 to 4.9 kHz with derating — higher frequencies reduce motor audible noise but derate the output current. For a furnace fan or kiln exhaust, 2 kHz is typical; for a quieter environment, 4 kHz is common but expect a current reduction. The integrated EMC filter meets IEC 61800-3 category C3 for a 300 m motor cable, covering most industrial installations without an external filter. For longer cable runs or stricter emissions limits (category C2), an external output filter may be needed.

Safety and compliance

The drive also includes thermal protection, motor phase break detection, overcurrent between output phases and earth, short-circuit protection, DC bus overvoltage, line undervoltage, line phase loss, and overspeed detection — all listed as built-in protection types. Standards compliance covers IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonic limits), IEC 60721-3 (environmental), and UL 61800-5-1 (US listing).

Fieldbus and control integration

The drive has two option card slots (Slot A and Slot B) for communication modules: Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen (daisy chain RJ45, SUB-D 9, or screw terminals), plus digital/analog I/O extension and output relay extension modules. Onboard Ethernet supports Modbus TCP at 10/100 Mbit/s with half/full duplex and autonegotiation; Modbus serial runs at 4.8 to 38.4 kbit/s on a 2-wire RS-485 bus with RTU framing, addressing 1 to 247 slaves. The control terminal block uses removable screw terminals for 0.5 to 1.5 mm² (AWG 20 to 16). Line-side connection is screw terminal; motor connection uses M10 bars.

Cabinet-mount only, with UL Type 1 and Type 12 ratings for cabinet integration. Forced-convection cooling. Operating altitude up to 2000 m with current derating above 1000 m; relative humidity 5 to 95% without condensation; vibration resistance 1.5 mm peak-to-peak at 2–13 Hz and 0.5 gn at 13–200 Hz; shock resistance 4 gn for 11 ms.

MPN
ATV6B0M10T6