Skip to main content
Schneider Electric ATV9A0C80Q4

Schneider ATV9A0C80Q4 Altivar Process ATV900, 800 kW Normal

MPN ATV9A0C80Q4
Active

Schneider Electric Altivar Process ATV900, modular variable speed drive, ATV9A0C80Q4, 800 kW normal duty / 630 kW heavy duty at 400 V, 1335 A line current, IP00, forced convection cooling.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV9A0C80Q4 specifications
ParameterValue
Connector type2 RJ45 for Ethernet IP/Modbus TCP on the control block 1 RJ45 for Modbus serial on the control block
Main product or component typeVariable speed drive
Current1335.0 A at 400 V (normal duty) 1061.0 A at 400 V (heavy duty)
Frequency50...60 Hz +/- 5 %
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min1.2 °C
Storage temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Data format8 bits, configurable odd, even or no parity for Modbus serial

Product details

Sizing and duty

The ATV9A0C80Q4: Normal duty delivers 800 kW at 400 V with 925 kVA apparent power; heavy duty drops to 630 kW and 735 kVA. The switching frequency is adjustable from 2 to 8 kHz with derating — the default 2.5 kHz gives full rated current. Prospective line short-circuit current is 50 kA, so the drive can be installed on high-capacity distribution without additional upstream limiting.

Control and safety

The control supply is 24 V DC for digital inputs (19…30 V range) and a separate 24 V DC rail (21…27 V) for STO and digital input power. An internal 10.5 V DC reference is provided for a 1 to 10 kΩ potentiometer. The drive carries CE marking and complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1.

Fieldbus and I/O expansion

The control block has two RJ45 ports for Ethernet IP/Modbus TCP (10/100 Mbit/s, half/full duplex, autonegotiation) and one RJ45 for Modbus serial (RTU, 4.8 to 38.4 kbit/s, 2-wire RS-485). Slot A accepts Profibus DP V1, PROFINET, DeviceNet, EtherCAT, or CANopen modules. Slots A, B, and C accept digital/analog I/O extension or output relay modules; slot B also takes 5/12 V digital encoder, analog encoder, or resolver interface modules. This means the drive can be configured for multi-protocol control cabinets without a separate gateway.

MPN
ATV9A0C80Q4