Skip to main content
Schneider Electric C080H460FM

Schneider Electric C080H460FM ComPacT NS Circuit Breaker, 80

MPN C080H460FM
Active

Schneider Electric ComPacT NS new generation, manually operated circuit breaker, 4 poles, 800 A at 50 °C, MicroLogic 6.0 electronic trip unit, 85 kA Icu at 220/240 V AC.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C080H460FM key specifications
ParameterValue
Control typeManually operated
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Utilization categoryCategory B
IP ratingIP40
Terminal pitch70 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

C080H460FM additional specifications
ParameterValue
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degree3 conforming to IEC 60947
Depth147 mm
Width280 mm
Height327 mm
Electrical life cycles2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

It is a 4-pole, manually operated unit rated 800 A at 50 °C, fitted with a MicroLogic 6.0 electronic trip unit that provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground fault) protection. Its breaking capacity reaches 85 kA Icu at 220/240 V AC and 70 kA Icu at 380/415 V AC, both per IEC 60947-2.

The 800 A trip unit rating at 50 °C sets the continuous current capacity. The electronic trip unit includes thermal memory (20 min) that retains heat history after a trip. Breaking capacity varies by voltage: 85 kA at 240 V, 70 kA at 415 V, 65 kA at 440 V, 50 kA at 525 V, and 42 kA at 690 V. For a 415 V system, the 70 kA Icu provides ample headroom for most industrial installations; coordination studies should verify selectivity with downstream devices. The breaker is rated IP40 (finger protection) and IK07 (impact resistance to 2 J), suitable for indoor panel environments.

MPN