Schneider Electric C080H460FM — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C080H460FM ComPacT NS Circuit Breaker, 80

MPNC080H460FM
Active

Schneider Electric ComPacT NS new generation, manually operated circuit breaker, 4 poles, 800 A at 50 °C, MicroLogic 6.0 electronic trip unit, 85 kA Icu at 220/240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C080H460FM — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C080H460FM — Electrical Ratings
ParameterValue
Rated current (In)800 A at 50 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Number of poles4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Overvoltage categoryIII
Electrical durability2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (operating cycles)10000 cycles
C080H460FM — Identification
ParameterValue
Product nameComPacT NS new generation
Product / component typeCircuit breaker
Product range / familyComPacT
C080H460FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
C080H460FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C080H460FM — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

It is a 4-pole, manually operated unit rated 800 A at 50 °C, fitted with a MicroLogic 6.0 electronic trip unit that provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground fault) protection. Its breaking capacity reaches 85 kA Icu at 220/240 V AC and 70 kA Icu at 380/415 V AC, both per IEC 60947-2.

The 800 A trip unit rating at 50 °C sets the continuous current capacity. The electronic trip unit includes thermal memory (20 min) that retains heat history after a trip. Breaking capacity varies by voltage: 85 kA at 240 V, 70 kA at 415 V, 65 kA at 440 V, 50 kA at 525 V, and 42 kA at 690 V. For a 415 V system, the 70 kA Icu provides ample headroom for most industrial installations; coordination studies should verify selectivity with downstream devices. The breaker is rated IP40 (finger protection) and IK07 (impact resistance to 2 J), suitable for indoor panel environments.

Frequently asked questions

What is the breaking capacity of C080H460FM at 415 V?

70 kA Icu at 380/415 V AC per IEC 60947-2.

What protection functions does the MicroLogic 6.0 trip unit provide?

It provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground fault) protection.

MPN