Skip to main content
Schneider Electric C1034A040

C1034A040 ComPacT NSX MicroLogic 4.2 AL Trip Unit, 40 A, 3P

MPN C1034A040
Obsolete

Schneider Electric ComPacT NSX100...250 series, MicroLogic 4.2 AL electronic trip unit, 40 A at 40 °C, 3-pole 3D, LSoI protection with integrated earth-leakage, EN/IEC 60947-2.

$10.42 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C1034A040 specifications
ParameterValue
Trip unit typeElectronic
Main product or component typeTrip unit
Voltage440 V AC 50/60 Hz
IP ratingIP40
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
ApplicationDistribution
Operating temperature-25...70 °C

Product details

MicroLogic 4.2 AL trip unit for ComPacT NSX100...250

The Schneider Electric C1034A040 is a MicroLogic 4.2 AL electronic trip unit for the ComPacT NSX100...250 range of molded-case circuit breakers. It is a 3-pole (3D protected) unit rated at 40 A at 40 °C, with an operational voltage of 440 V AC at 50/60 Hz. The trip unit provides LSoI protection: long-time overload (L), short-time short-circuit with fixed delay (So), and instantaneous short-circuit (I), plus integrated earth-leakage protection (Class A).

Protection settings and adjustability

The long-time pickup Ir is adjustable across 9 settings from 18 to 40 A, with fixed delay curves: 400 s at 1.5 x Ir, 16 s at 6 x Ir, and 11 s at 7.2 x Ir. Short-time pickup Isd adjusts from 1.5 to 10 x Ir, with a fixed delay. Instantaneous pickup Ii is fixed at 600 A. Earth-leakage sensitivity IΔn and time delay Δt are both adjustable, with Δt selectable from 0 ms, 60 ms, 150 ms, 500 ms, or 1 s.

The trip unit is designed to EN/IEC 60947-2, with a pollution degree of 3 per IEC 60947-1 and IP40 front-face protection per IEC 60529. The unit is Class II for electrical shock protection.

This is a fixed-mount trip unit for the ComPacT NSX100...250 breaker frame. It occupies the standard 3-pole slot and communicates local status via a flashing green LED (ready), red LED at 105% Ir (overload), orange LED at 90% Ir (pre-alarm), and a yellow indicator for residual current. No zone selective interlocking (ZSI) is provided on this variant. The earth-leakage function can be disabled via the IΔn rotary switch for applications where ground-fault coordination is handled upstream.