Schneider Electric C1047A100

Schneider Electric C1047A100 MicroLogic 7.2 E AL Trip Unit,

MPN C1047A100
Active

Schneider Electric ComPacT NSX100...250, MicroLogic 7.2 E AL electronic trip unit, 100 A at 40 °C, 4P, LSI protection with integrated earth-leakage, EN/IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C1047A100 specifications
ParameterValue
Display typeLCD display
Trip unit typeElectronic
Main product or component typeTrip unit
Voltage440 V AC 50/60 Hz
IP ratingIP40
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C1047A100 is a MicroLogic 7.2 E AL electronic trip unit designed for the ComPacT NSX100...250 molded-case circuit breaker frame. The LCD display gives you local readout of energy metering, demand values, and event logs — no separate meter module needed.

The long-time pickup (Ir) is adjustable from 40 to 100 A, so you can tune it to the actual load without swapping the trip unit. Short-time (Isd) and instantaneous (Ii) are also adjustable, giving you selective coordination downstream. Integrated earth-leakage protection (Class A) covers sinusoidal AC and pulsating DC faults up to the breaker's rating. You can disable it via the IΔn rotary switch if the circuit doesn't need it. The trip unit also meets EN/IEC 60947-2, the standard for low-voltage switchgear — that's the compliance stamp for most industrial distribution panels.

Mounting and integration notes

The trip unit mounts fixed into the ComPacT NSX100...250 breaker frame — no DIN rail, it's a direct plug-in onto the breaker's base. The neutral is on the left side (4P configuration). IP40 protection means it's fine inside a standard IP54 or better enclosure; keep it out of washdown zones.

MPN