Skip to main content
Schneider Electric C1047A100 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C1047A100 MicroLogic 7.2 E AL Trip Unit,

MPNC1047A100
Active

Schneider Electric ComPacT NSX100...250, MicroLogic 7.2 E AL electronic trip unit, 100 A at 40 °C, 4P, LSI protection with integrated earth-leakage, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C1047A100 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C1047A100 — Electrical Ratings
ParameterValue
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
C1047A100 — Identification
ParameterValue
Product / component typeTrip unit
Product range / familyComPacT
C1047A100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-1
C1047A100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C1047A100 is a MicroLogic 7.2 E AL electronic trip unit designed for the ComPacT NSX100...250 molded-case circuit breaker frame. The LCD display gives you local readout of energy metering, demand values, and event logs — no separate meter module needed.

The long-time pickup (Ir) is adjustable from 40 to 100 A, so you can tune it to the actual load without swapping the trip unit. Short-time (Isd) and instantaneous (Ii) are also adjustable, giving you selective coordination downstream. Integrated earth-leakage protection (Class A) covers sinusoidal AC and pulsating DC faults up to the breaker's rating. You can disable it via the IΔn rotary switch if the circuit doesn't need it. The trip unit also meets EN/IEC 60947-2, the standard for low-voltage switchgear — that's the compliance stamp for most industrial distribution panels.

Mounting and integration notes

The trip unit mounts fixed into the ComPacT NSX100...250 breaker frame — no DIN rail, it's a direct plug-in onto the breaker's base. The neutral is on the left side (4P configuration). IP40 protection means it's fine inside a standard IP54 or better enclosure; keep it out of washdown zones.

Frequently asked questions

What standards does C1047A100 comply with?

It complies with EN/IEC 60947-2, the main standard for low-voltage switchgear and controlgear. It also carries pollution degree 3 per IEC 60947-1 and IP40 per IEC 60529.

What is the trip unit rating and adjustment range?

The trip unit is rated 100 A at 40 °C. The long-time pickup (Ir) adjusts from 40 to 100 A, short-time pickup (Isd) is adjustable, and instantaneous pickup (Ii) is adjustable. Long-time delay (Tr) ranges from 15 to 400 s at 1.5 x Ir, and short-time delay (tsd) from 0 to 0.4 s with I²t on or off.

Where can I buy C1047A100?

This part is sourced and quoted to order through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN
C1047A100