Skip to main content
Schneider Electric C106TM100C

C106TM100C ComPacT NSX Trip Unit TM-D, 100 A, 4P 3D

MPN C106TM100C
Active

Schneider Electric ComPacT NSX series, trip unit TM-D, thermal-magnetic, rating 100 A at 50 °C, 4 poles 3D, fixed mount, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C106TM100C specifications
ParameterValue
Trip unit typeThermal-magnetic
Main product or component typeTrip unit
Voltage690 V AC 50/60 Hz 750 V DC
IP ratingIP40
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degree3 conforming to IEC 60947-1
ApplicationDistribution
Operating temperature-25...70 °C

Product details

Trip unit for ComPacT NSX100…250

The C106TM100C is a thermal-magnetic trip unit from the Schneider Electric ComPacT NSX range, designed for the NSX100…250 frame. It carries a continuous rating of 100 A at 50 °C and protects a 4-pole circuit breaker with 3 protected poles (3D, neutral left, no neutral protection).

Protection settings and coordination

The long-time pickup Ir is adjustable from 0.7 to 1.0 x In (70–100 A), with a fixed delay of 120–400 s at 1.5 x Ir and 15 s at 6 x Ir. The instantaneous pickup Ii is fixed at 800 A — a multiple of 8 x In at the 100 A rating. This fixed Ii at 800 A means the unit clears a hard short without adjustment risk, but it also sets the selectivity floor: downstream devices must have an instantaneous threshold below 800 A to coordinate. For a panel designer, this is the number to check against the feeder breaker's magnetic trip.

MPN
C106TM100C