Skip to main content
Schneider Electric C106TM100C — Miniature Circuit Breakers (MCB)

C106TM100C ComPacT NSX Trip Unit TM-D, 100 A, 4P 3D

MPNC106TM100C
Active

Schneider Electric ComPacT NSX series, trip unit TM-D, thermal-magnetic, rating 100 A at 50 °C, 4 poles 3D, fixed mount, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C106TM100C — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NSX100...250
Product/component typeTrip unit
Device applicationDistribution
C106TM100C — Ratings
ParameterValue
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz 750 V DC
Network type (AC/DC)AC DC
Network frequency50/60 Hz
C106TM100C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
C106TM100C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-1
C106TM100C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C106TM100C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

Trip unit for ComPacT NSX100…250

The C106TM100C is a thermal-magnetic trip unit from the Schneider Electric ComPacT NSX range, designed for the NSX100…250 frame. It carries a continuous rating of 100 A at 50 °C and protects a 4-pole circuit breaker with 3 protected poles (3D, neutral left, no neutral protection).

Protection settings and coordination

The long-time pickup Ir is adjustable from 0.7 to 1.0 x In (70–100 A), with a fixed delay of 120–400 s at 1.5 x Ir and 15 s at 6 x Ir. The instantaneous pickup Ii is fixed at 800 A — a multiple of 8 x In at the 100 A rating. This fixed Ii at 800 A means the unit clears a hard short without adjustment risk, but it also sets the selectivity floor: downstream devices must have an instantaneous threshold below 800 A to coordinate. For a panel designer, this is the number to check against the feeder breaker's magnetic trip.

Frequently asked questions

What standards does C106TM100C comply with?

The C106TM100C complies with EN/IEC 60947-2, the international standard for low-voltage circuit breakers. It also meets pollution degree 3 per IEC 60947-1 and IP40 per IEC 60529.

How do I get current pricing and availability for C106TM100C?

Submit an RFQ through the storefront. This part is sourced to order via independent distribution; pricing and stock levels are confirmed at quote time. No public price or stock count is listed here.

MPN