Schneider Electric ComPacT NSX series, NSX100B, 4P, 100 A at 40 °C, MicroLogic 2.2 electronic trip unit, 25 kA Icu at 415 V AC.

$370.00 – $703.51 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10B42D100 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C10B42D100 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical life cycles50000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric C10B42D100 is a ComPacT NSX100B 4-pole circuit breaker with a 100 A rating at 40 °C, fitted with a MicroLogic 2.2 electronic trip unit. It delivers 25 kA Icu at 415 V AC, 50/60 Hz per IEC 60947-2 — the standard for low-voltage industrial power circuit breakers. The breaker sits in the ComPacT NSX family, a widely deployed platform for panelboard and switchboard applications.

MicroLogic 2.2 trip unit and protection curves

The electronic MicroLogic 2.2 trip unit provides three protection functions: L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit). So protection with a fixed delay allows selective coordination with downstream breakers, provided the delay is set longer than the downstream clearing time. The I setting clears hard faults instantaneously. This is a Category A breaker (per IEC 60947-2), meaning it is not specifically intended for selectivity under short-circuit conditions with other Category A breakers — coordination study is recommended.

Breaking capacity across voltage levels

The breaking capacity varies with system voltage: 40 kA Icu at 220/240 V AC, 25 kA at 380/415 V AC, 20 kA at 440 V AC, and 15 kA at 500 V AC. At 480 V (common in North American 277/480 V systems), the 440 V rating applies — 20 kA Icu — which covers typical available fault currents in commercial and light industrial distribution.

Physical integration and mounting

Mounts on a backplate in either horizontal or vertical orientation, flat on the back. The 4-pole form factor with neutral on the left occupies four 35 mm pitch module spaces. Front connections (both upside and downside) simplify busbar wiring in a panel.