Skip to main content
Schneider Electric C10B42D100 — Miniature Circuit Breakers (MCB)

Schneider Electric C10B42D100 ComPacT NSX100B Circuit Breake

MPNC10B42D100
Active

Schneider Electric ComPacT NSX series, NSX100B, 4P, 100 A at 40 °C, MicroLogic 2.2 electronic trip unit, 25 kA Icu at 415 V AC.

$370.00 – $703.51Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C10B42D100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10B42D100 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration4P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 7 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10B42D100 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10B42D100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10B42D100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10B42D100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10B42D100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range40...100 A
Trip unit protection functionsLSoI

Product details

The Schneider Electric C10B42D100 is a ComPacT NSX100B 4-pole circuit breaker with a 100 A rating at 40 °C, fitted with a MicroLogic 2.2 electronic trip unit. It delivers 25 kA Icu at 415 V AC, 50/60 Hz per IEC 60947-2 — the standard for low-voltage industrial power circuit breakers. The breaker sits in the ComPacT NSX family, a widely deployed platform for panelboard and switchboard applications.

MicroLogic 2.2 trip unit and protection curves

The electronic MicroLogic 2.2 trip unit provides three protection functions: L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit). So protection with a fixed delay allows selective coordination with downstream breakers, provided the delay is set longer than the downstream clearing time. The I setting clears hard faults instantaneously. This is a Category A breaker (per IEC 60947-2), meaning it is not specifically intended for selectivity under short-circuit conditions with other Category A breakers — coordination study is recommended.

Breaking capacity across voltage levels

The breaking capacity varies with system voltage: 40 kA Icu at 220/240 V AC, 25 kA at 380/415 V AC, 20 kA at 440 V AC, and 15 kA at 500 V AC. At 480 V (common in North American 277/480 V systems), the 440 V rating applies — 20 kA Icu — which covers typical available fault currents in commercial and light industrial distribution.

Physical integration and mounting

Mounts on a backplate in either horizontal or vertical orientation, flat on the back. The 4-pole form factor with neutral on the left occupies four 35 mm pitch module spaces. Front connections (both upside and downside) simplify busbar wiring in a panel.

Frequently asked questions

What is the breaking capacity of C10B42D100 at 415 V?

The C10B42D100 delivers 25 kA Icu at 380/415 V AC, 50/60 Hz per IEC 60947-2. This corresponds to the B breaking capacity code. At 440 V AC the rating is 20 kA Icu; at 500 V AC it is 15 kA Icu.

What trip unit does the C10B42D100 use?

It uses a MicroLogic 2.2 electronic trip unit providing L (long-time overload with thermal memory), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit) protection functions.

Where can I buy the C10B42D100 and what is the lead time?

The C10B42D100 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote — no stock count or lead-time number is published here. Submit an RFQ for a firm commitment.

MPN
C10B42D100