Skip to main content
Schneider Electric C10F3MA003

Schneider C10F3MA003 ComPacT NSX100F, 2.5 A MA Trip, 85 kA I

MPN C10F3MA003
Active

Schneider Electric ComPacT NSX NSX100F, 3-pole, 2.5 A MA magnetic-only trip unit, 85 kA Icu at 240 V AC, motor protection application.

$303.69 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10F3MA003 key specifications
ParameterValue
Control typeToggle
Trip unit typeMagnetic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C10F3MA003 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical life cycles50000 cycles
ApplicationMotor protection
Operating temperature-25...70 °C

Product details

It is designed specifically for motor protection — the MA trip responds only to short-circuit (magnetic) faults, not overloads, so the motor's own overload relay handles thermal protection. The 2.5 A rating at 65 °C means the trip unit is calibrated for that current at elevated ambient temperature — important when the breaker is inside a warm enclosure. The magnetic-only characteristic (no thermal bimetal) makes this unsuitable for cable or general distribution protection; it belongs on a motor branch circuit where a separate overload relay provides the thermal element.

Front connection both top and bottom; connection pitch is 35 mm.

Overvoltage category III, utilisation category A. IP40 finger protection, IK07 impact resistance. The manufacturer provides the usual compliance documentation (declaration of conformity, test certificates) on request for FAT/SAT packages.

MPN
C10F3MA003