Skip to main content
Schneider Electric C10H34V100

C10H34V100 ComPacT NSX Earth Leakage Breaker, 100 A, 100 kA

MPN C10H34V100
Obsolete

Schneider Electric ComPacT NSX, earth leakage circuit breaker, 3P, 100 A at 40 °C, MicroLogic 4.2 electronic trip unit, 100 kA Icu at 240 V AC, EN/IEC 60947-2.

$1,063.78 – $2,067.12 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10H34V100 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C10H34V100 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical life cycles50000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric C10H34V100 is a ComPacT NSX earth leakage circuit breaker (ELCB) with a MicroLogic 4.2 electronic trip unit, rated 100 A at 40 °C. It provides overload (L), short-time short-circuit (So), instantaneous short-circuit (I), and integrated earth-leakage (R) protection in a 3-pole, 105 mm wide package for backplate mounting. The H breaking capacity code delivers 70 kA Icu at 415 V AC per IEC 60947-2, and 100 kA Icu at 240 V AC — enough headroom for most distribution panel main or feeder positions without cascading upstream.

Above that, the electronic trip unit thermally models the conductor — the 20-minute thermal memory means it remembers prior heating even after a trip resets, so re-energizing a hot circuit won't nuisance-trip on the second start. Integrated earth-leakage protection (R function) means no external RCM or toroid is needed — the MicroLogic 4.2 handles ground-fault sensing internally. The OFF position is set via the IΔn rotary switch, which lets you select the residual sensitivity without opening the cover.

Deployment context

Backplate-mounted in a distribution panel with front-facing connections top and bottom.

MPN