Skip to main content
Schneider Electric C10H3MA007

Schneider C10H3MA007 ComPacT NSX100H, 6.3 A MA Trip, 100 kA

MPN C10H3MA007
Active

Schneider Electric ComPacT NSX NSX100H, circuit breaker, 3P, 6.3 A MA magnetic trip unit, 100 kA Icu at 240 V AC, 70 kA at 415 V AC, EN/IEC 60947-2.

$340.07 – $558.95 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10H3MA007 key specifications
ParameterValue
Control typeToggle
Trip unit typeMagnetic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C10H3MA007 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical life cycles50000 cycles
ApplicationMotor protection
Operating temperature-25...70 °C

Product details

The Schneider Electric C10H3MA007 is a ComPacT NSX100H circuit breaker with a magnetic-only MA trip unit rated 6.3 A at 65 °C. It is designed specifically for motor protection — the MA trip provides short-circuit (magnetic) protection only, with no thermal overload element, so it pairs with an external overload relay to handle the motor's running overcurrent protection. The 3-pole device carries a 100 kA Icu breaking capacity at 240 V AC and 70 kA at 415 V AC, both per IEC 60947-2, which means it can safely interrupt fault currents up to those levels without upstream cascading. It also carries UL 60947-4-1 ratings of 85 kA at 240 V and 65 kA at 480 V, covering North American motor branch-circuit installations.

If your panel ambient is lower, the breaker can carry slightly more; if higher, you derate. The MA trip unit's magnetic pickup is fixed (not adjustable), so verify the motor's locked-rotor current falls within the breaker's instantaneous trip band. The NSX100H frame accepts plug-in trip units and auxiliary accessories via its 5 accessory slots, so adding shunt trips, aux contacts, or an earth-leakage module later is straightforward.

The 105 mm width, 161 mm height, and 86 mm depth fit standard ComPacT NSX cutouts. IK07 impact resistance handles incidental tool contact during maintenance.

Electrical durability and isolation

Rated for 50,000 mechanical cycles and 30,000 electrical cycles at 440 V at rated current. At half-rated current (In/2), electrical durability rises to 50,000 cycles at 440 V and 20,000 cycles at 690 V. Power dissipation is 3.93 W per pole — roughly 12 W total at rated load, which matters for panel thermal calculations.

MPN