Skip to main content
Schneider Electric C10N3MA013

Schneider Electric C10N3MA013 ComPacT NSX100N, 12.5 A, 50 kA

MPN C10N3MA013
Active

Schneider Electric ComPacT NSX, NSX100N, circuit breaker, 3P, 12.5 A, MA magnetic trip unit, 50 kA at 415 V AC.

$321.02 – $503.77 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10N3MA013 key specifications
ParameterValue
Control typeToggle
Trip unit typeMagnetic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C10N3MA013 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical life cycles50000 cycles
ApplicationMotor protection
Operating temperature-25...70 °C

Product details

Motor protection circuit breaker, magnetic-only trip

The Schneider Electric C10N3MA013 is a ComPacT NSX100N circuit breaker with a magnetic-only (MA) trip unit, rated 12.5 A at 65 °C. It is designed specifically for motor protection, providing short-circuit protection via magnetic sensing without thermal overload elements — the motor starter or overload relay handles the thermal curve. The 3-pole device carries a 50 kA breaking capacity at 415 V AC (Icu per IEC 60947-2), which means it can safely interrupt fault currents up to that level in a 400 V motor branch circuit without upstream coordination failure.

Breaking capacity and application context

The N-frame (NSX100N) delivers 90 kA Icu at 240 V AC and 50 kA at 415 V AC, tapering to 10 kA at 690 V AC. For a 400 V motor panel, the 50 kA symmetrical rating covers most industrial service-entrance and distribution scenarios. The MA trip unit responds only to magnetic faults — set the instantaneous pickup per the motor inrush and the upstream coordination study. Mounts on a backplate, accepts front-front connections, and fits in a 105 mm wide footprint.

Durability and environmental ratings

Rated for 50,000 mechanical cycles and 50,000 electrical cycles at 440 V at half rated current (In/2). Electrical durability drops to 10,000 cycles at 690 V at full In. IP40 front protection and IK07 impact resistance handle typical panel environments. Operating altitude to 2000 m without derating; derate above that per the manufacturer's curve. Power dissipation is 0.63 W per pole — negligible for enclosure thermal calculations.

MPN