Skip to main content
Schneider Electric C10R36E040

Schneider Electric C10R36E040 ComPacT NSX 40A, 200 kA 415V

MPN C10R36E040
Active

Schneider Electric ComPacT NSX, NSX100R, 3P, 40 A, 200 kA Icu at 415 V AC, MicroLogic 6.2 E electronic trip unit, LCD display, toggle control.

$23.78 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10R36E040 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
Breaking capacity200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

C10R36E040 additional specifications
ParameterValue
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric C10R36E040 is a ComPacT NSX100R molded case circuit breaker, part of the ComPacT NSX family, fitted with a MicroLogic 6.2 E electronic trip unit rated at 40 A at 40 °C. This is a three-pole (3P) breaker built to EN/IEC 60947-2, with a breaking capacity code of R — meaning 200 kA Icu at 415 V AC, 50/60 Hz. The 200 kA figure holds at 220/240 V and 380/415 V as well, then steps down to 80 kA at 500 V and 45 kA at 690 V. That kind of headroom makes it a strong choice for high-fault distribution boards where you need selectivity without cascading upstream.

Mounts on a backplate — no DIN rail here. The 105 mm width, 161 mm height, and 86 mm depth fit a standard ComPacT NSX cutout.

The MicroLogic 6.2 E trip unit gives you LSI protection (long-time overload, short-time short-circuit, instantaneous short-circuit) plus ground-fault (G) protection. It's electronic, so you get adjustable curves and an LCD display for reading trip causes, energy metering, and event logs.

Electrical durability is rated at 10,000 cycles at 440 V at full rated current (In), and 20,000 cycles at half current. Operating altitude: 0–2000 m without derating, up to 5000 m with derating.

MPN