Skip to main content
Schneider Electric C10R36E040 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C10R36E040 ComPacT NSX 40A, 200 kA 415V

MPNC10R36E040
Obsolete

Schneider Electric ComPacT NSX, NSX100R, 3P, 40 A, 200 kA Icu at 415 V AC, MicroLogic 6.2 E electronic trip unit, LCD display, toggle control.

$23.78Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10R36E040 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10R36E040 — Electrical Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C10R36E040 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX100R
C10R36E040 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C10R36E040 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C10R36E040 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The Schneider Electric C10R36E040 is a ComPacT NSX100R molded case circuit breaker, part of the ComPacT NSX family, fitted with a MicroLogic 6.2 E electronic trip unit rated at 40 A at 40 °C. This is a three-pole (3P) breaker built to EN/IEC 60947-2, with a breaking capacity code of R — meaning 200 kA Icu at 415 V AC, 50/60 Hz. The 200 kA figure holds at 220/240 V and 380/415 V as well, then steps down to 80 kA at 500 V and 45 kA at 690 V. That kind of headroom makes it a strong choice for high-fault distribution boards where you need selectivity without cascading upstream.

Mounts on a backplate — no DIN rail here. The 105 mm width, 161 mm height, and 86 mm depth fit a standard ComPacT NSX cutout.

The MicroLogic 6.2 E trip unit gives you LSI protection (long-time overload, short-time short-circuit, instantaneous short-circuit) plus ground-fault (G) protection. It's electronic, so you get adjustable curves and an LCD display for reading trip causes, energy metering, and event logs.

Electrical durability is rated at 10,000 cycles at 440 V at full rated current (In), and 20,000 cycles at half current. Operating altitude: 0–2000 m without derating, up to 5000 m with derating.

Frequently asked questions

Where can I buy C10R36E040 and get a price?

The C10R36E040 is available to order against an RFQ. Submit a request for current pricing and availability — confirmed at quote time.

What is the breaking capacity of this breaker at 415 V?

200 kA Icu at 380/415 V AC, 50/60 Hz, conforming to IEC 60947-2. That's the R breaking capacity code.

What compliance standards does the C10R36E040 meet?

It is certified to EN/IEC 60947-2, with pollution degree 3 per IEC 60664-1 and overvoltage category III.

MPN
C10R36E040