Skip to main content
Schneider Electric C10R36E100

Schneider Electric C10R36E100 ComPacT NSX 100A, 200kA, Micro

MPN C10R36E100
Active

Schneider Electric ComPacT NSX, NSX100R, 3P, 100 A at 40 °C, MicroLogic 6.2 E trip unit, 200 kA Icu at 415 V AC, electronic LSIG protection.

$2,094.11 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10R36E100 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-40 °C

All specifications

C10R36E100 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C10R36E100 is a 3-pole ComPacT NSX100R molded-case circuit breaker with a MicroLogic 6.2 E electronic trip unit, rated 100 A at 40 °C. The MicroLogic 6.2 E provides LSIG protection: L (long-time overload), S (short-time short-circuit with adjustable delay for selectivity), I (instantaneous short-circuit), and G (ground-fault). The electronic trip unit also logs energy metering, time-stamped event histories, demand current, and power quality data — communicated via the front LCD display and maintenance indicators. This makes it a fit for distribution panels where both protection coordination and energy monitoring are required on the same breaker.

Front connection on both upside and downside simplifies bus-bar or cable routing in a distribution switchboard. The toggle control and LCD display are front-accessible. Five accessory slots allow field-installable aux contacts, shunt trips, or communication modules. IP40 front protection keeps out tools and fingers; IK07 impact resistance handles accidental panel-door strikes.

MPN
C10R36E100