Schneider Electric C10R36E100 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C10R36E100 ComPacT NSX 100A, 200kA, Micro

MPNC10R36E100
Active

Schneider Electric ComPacT NSX, NSX100R, 3P, 100 A at 40 °C, MicroLogic 6.2 E trip unit, 200 kA Icu at 415 V AC, electronic LSIG protection.

$2,094.11Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10R36E100 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10R36E100 — Electrical Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C10R36E100 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX100R
C10R36E100 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C10R36E100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C10R36E100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C10R36E100 is a 3-pole ComPacT NSX100R molded-case circuit breaker with a MicroLogic 6.2 E electronic trip unit, rated 100 A at 40 °C. The MicroLogic 6.2 E provides LSIG protection: L (long-time overload), S (short-time short-circuit with adjustable delay for selectivity), I (instantaneous short-circuit), and G (ground-fault). The electronic trip unit also logs energy metering, time-stamped event histories, demand current, and power quality data — communicated via the front LCD display and maintenance indicators. This makes it a fit for distribution panels where both protection coordination and energy monitoring are required on the same breaker.

Front connection on both upside and downside simplifies bus-bar or cable routing in a distribution switchboard. The toggle control and LCD display are front-accessible. Five accessory slots allow field-installable aux contacts, shunt trips, or communication modules. IP40 front protection keeps out tools and fingers; IK07 impact resistance handles accidental panel-door strikes.

Frequently asked questions

Where can I buy C10R36E100 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

What are the key protection functions of the MicroLogic 6.2 E trip unit?

The MicroLogic 6.2 E provides LSIG protection: L for overload (long-time), S for short-time short-circuit with adjustable delay, I for instantaneous short-circuit, and G for ground-fault. It also logs energy metering, time-stamped events, and power quality data via the LCD display.

What breaking capacity does C10R36E100 have at 415 V?

It is rated 200 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, which is the highest breaking capacity code ('R') in the NSX100 family.

What compliance documentation is available for C10R36E100?

The breaker is certified to EN/IEC 60947-2. The IP40 and IK07 ratings per IEC 60529 and IEC 62262 are documented. Pollution degree 3 per IEC 60664-1 is specified.