Skip to main content
Schneider Electric C10R36M080

Schneider Electric C10R36M080 ComPacT NSX MCCB, 80 A, 200 kA

MPN C10R36M080
Active

Schneider Electric ComPacT NSX, C10R36M080, 3P MCCB with MicroLogic 6.2 E-M electronic trip unit, 80 A rated, 200 kA Icu at 415 V AC, motor protection.

$23.28 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10R36M080 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
Breaking capacity200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

C10R36M080 additional specifications
ParameterValue
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationMotor protection
Operating temperature-25...70 °C

Product details

The Schneider Electric C10R36M080 is a ComPacT NSX100R three-pole molded-case circuit breaker with a MicroLogic 6.2 E-M electronic trip unit, rated 80 A at 65 °C. It is designed for motor protection — the E-M trip curve provides long-time (L), short-time (So), instantaneous (I), and ground-fault (G) protection, with selectable motor tripping classes 5, 10, 20, and 30.

Mounting and integration details

The LCD display on the MicroLogic trip unit shows energy metering, protection settings, and event logs; the green flashing LED indicates ready state, red LED signals overtemperature at 95 % Ith.

Durability and thermal memory

Mechanical endurance is 20,000 cycles; electrical durability at rated current (80 A, 440 V) is 10,000 cycles, doubling to 20,000 cycles at half-load. The 20-minute thermal memory before and after tripping means the breaker's thermal model retains heat history for that window — useful for re-closing on a motor that has just tripped on overload, avoiding nuisance trips if the motor has not cooled.

MPN
C10R36M080