Skip to main content
Schneider Electric C10R36M080 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C10R36M080 ComPacT NSX MCCB, 80 A, 200 kA

MPNC10R36M080
Active

Schneider Electric ComPacT NSX, C10R36M080, 3P MCCB with MicroLogic 6.2 E-M electronic trip unit, 80 A rated, 200 kA Icu at 415 V AC, motor protection.

$23.28Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10R36M080 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
C10R36M080 — Electrical Ratings
ParameterValue
Rated current (In)80 A at 65 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C10R36M080 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX100R
C10R36M080 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C10R36M080 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C10R36M080 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The Schneider Electric C10R36M080 is a ComPacT NSX100R three-pole molded-case circuit breaker with a MicroLogic 6.2 E-M electronic trip unit, rated 80 A at 65 °C. It is designed for motor protection — the E-M trip curve provides long-time (L), short-time (So), instantaneous (I), and ground-fault (G) protection, with selectable motor tripping classes 5, 10, 20, and 30.

Mounting and integration details

The LCD display on the MicroLogic trip unit shows energy metering, protection settings, and event logs; the green flashing LED indicates ready state, red LED signals overtemperature at 95 % Ith.

Durability and thermal memory

Mechanical endurance is 20,000 cycles; electrical durability at rated current (80 A, 440 V) is 10,000 cycles, doubling to 20,000 cycles at half-load. The 20-minute thermal memory before and after tripping means the breaker's thermal model retains heat history for that window — useful for re-closing on a motor that has just tripped on overload, avoiding nuisance trips if the motor has not cooled.

Frequently asked questions

Where can I buy C10R36M080 and get a price?

The C10R36M080 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of C10R36M080 at 415 V?

200 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 690 V AC it derates to 45 kA Icu.

What motor tripping classes does the MicroLogic 6.2 E-M support?

Selectable classes 5, 10, 20, and 30, covering fast (5) to slow (30) overload curves for different motor thermal time constants.

What compliance documentation is available for C10R36M080?

The breaker is certified to EN/IEC 60947-2, carries pollution degree 3 per IEC 60664-1, and is rated IK07 impact protection per IEC 62262.

MPN