Skip to main content
Schneider Electric C10V3MA050

C10V3MA050 ComPacT NSX circuit breaker, 50 A, 85 kA Icu, mag

MPN C10V3MA050
Active

Schneider Electric ComPacT NSX, circuit breaker, 3P, 50 A, MA magnetic-only trip unit, 85 kA Icu at 500 V AC, EN/IEC 60947-2.

$6.53 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10V3MA050 key specifications
ParameterValue
Control typeToggle
Trip unit typeMagnetic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
Breaking capacity85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C10V3MA050 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationMotor protection
Operating temperature-25...70 °C

Product details

It is a 3-pole device (3P) built to EN/IEC 60947-2, intended for motor protection where only short-circuit (magnetic) protection is required — no thermal overload element. The MA trip unit responds to fault currents only; motor overload protection is handled separately by a thermal relay or motor protection relay in the circuit.

Breaking capacity and isolation

Rated breaking capacity reaches 85 kA Icu at 500 V AC 50/60 Hz, 80 kA Icu at 525 V AC, and 75 kA Icu at 660/690 V AC — the HB1 breaking capacity code.

Mounts on a backplate — flat on the back, horizontal or vertical orientation accepted. The front connection (upside and downside) uses a 35 mm connection pitch. IP40 enclosure protection keeps out tools and particles >1 mm; IK07 impact resistance handles a 2 J drop. Operating altitude derating begins above 2000 m.

No earth-leakage protection built in (no Vigi module). Relative humidity range 0–95 %. The toggle control is manual; no auxiliary contacts or shunt trip are included in this base variant.

MPN