Skip to main content
Schneider Electric C10W46E040

C10W46E040 ComPacT NSX 40A 4P MCCB, 100 kA Icu 690 V AC

MPN C10W46E040
Active

C10W46E040, Schneider Electric ComPacT NSX, 40 A, 4P, MicroLogic 6.2 E electronic trip unit, 100 kA Icu at 690 V AC, EN/IEC 60947-2.

$15.26 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10W46E040 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
Breaking capacity100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

C10W46E040 additional specifications
ParameterValue
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C10W46E040 is a Schneider Electric ComPacT NSX moulded-case circuit breaker rated 40 A at 40 °C, 4-pole, with a MicroLogic 6.2 E electronic trip unit. The 100 kA Icu at 690 V AC per IEC 60947-2 means it can safely interrupt fault currents up to that level on a 690 V line without upstream cascading — the HB2 breaking capacity code confirms that. The 6.2 E trip provides L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground-fault) protection, plus an energy-meter function and LCD display for time-stamped event logs and power-quality data.

Selectivity and coordination

The electronic trip unit's LSI+G curves give the site engineer fine-grained selectivity with downstream breakers.

Four poles with neutral on the left. The 161 x 140 x 86 mm (H x W x D) footprint fits standard panel layouts.

MPN