Schneider Electric C11F34V025B

Schneider Electric C11F34V025B ComPacT NSXm, 25 A, 3P, 36 kA

MPN C11F34V025B
Active

Schneider Electric ComPacT NSXm, 25 A, 3P, 36 kA at 415 V AC, MicroLogic 4.1 electronic trip unit, earth-leakage protection, EN/IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C11F34V025B key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm with spreaders 27 mm without spreaders
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C

All specifications

C11F34V025B additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
ColorGrey (RAL 7016)
Depth80 mm
Width108 mm
Height144 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Safety categoryF 36 kA 415 V AC
Operating temperature-25...70 °C

Product details

What it is and what it does

The Schneider Electric C11F34V025B is a ComPacT NSXm moulded-case circuit breaker (MCCB) with integrated earth-leakage protection, built to EN/IEC 60947-2. It carries a MicroLogic 4.1 electronic trip unit rated 25 A at 40 °C, three poles, and a breaking capacity of 36 kA at 415 V AC — the F performance level in the NSXm 63F frame. This is the version with the grey (RAL 7016) operating handle and front-connect terminals. The 36 kA at 415 V AC means it can safely interrupt a fault current up to that level without upstream fuses or a larger breaker — sized for distribution panels where the available fault current is known to be under that threshold. The electronic trip unit adds thermal memory (20 minutes before and after tripping), which prevents nuisance reclosing on a hot cable. Integrated earth-leakage protection is selectable: class A or class AC, with sensitivity from 30 mA up to 5 A. That covers both personnel protection (30 mA) and equipment ground-fault detection at higher thresholds. The breaker itself is category A (no intentional short-time delay), so it coordinates with downstream devices on a selective scheme.

Mounting and integration

Mounts on a backplate — horizontal or vertical, flat against the surface. The 9-module pitch (9 x 9 mm = 81 mm) and overall dimensions of 108 mm wide, 144 mm high, 80 mm deep fit standard ComPacT NSXm cutouts. Connection pitch is 35 mm with spreaders, 27 mm without. Front-connect terminals accept compression lugs or busbars. IP40 enclosure protection and IK07 impact resistance are adequate for panel-mount indoor use — not for washdown or outdoor exposure. Pollution degree 3 (conductive pollution or dry non-conductive that becomes conductive) and overvoltage category IV (equipment at the origin of the installation) match typical distribution switchboard conditions.

MPN