Skip to main content
Schneider Electric C11H44V025L

C11H44V025L ComPacT NSXm MCCB, 25 A, 4P, 70 kA

MPN C11H44V025L
Active

Schneider Electric ComPacT NSXm, 25 A, 4P, MicroLogic 4.1 electronic trip unit, 70 kA at 415 V AC, integrated earth-leakage, C11H44V025L.

$853.85 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C11H44V025L key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm with spreaders 27 mm without spreaders
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C

All specifications

C11H44V025L additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
ColorGrey (RAL 7016)
Depth80 mm
Width108 mm
Height144 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Safety categoryH 70 kA 415 V AC
Operating temperature-25...70 °C

Product details

The C11H44V025L is a Schneider Electric ComPacT NSXm moulded-case circuit breaker, 4-pole, rated 25 A at 40 °C with a MicroLogic 4.1 electronic trip unit.

Integrated earth-leakage and trip-unit detail

Earth-leakage protection is integrated into the breaker, with selectable sensitivity from 30 mA to 5 A for both class A and class AC residual currents. The breaker is utilisation category A, meaning it is not intended for frequent switching of motor starts but for distribution-circuit protection where fault interruption is the primary duty.

Mounting and integration notes

Mounts on a backplate in horizontal or vertical orientation. The 9 mm pitch footprint occupies 12 modules — 108 mm wide, 144 mm high, 80 mm deep. Front-facing connections top and bottom accept Everlink lugs for copper or aluminium conductors up to 95 mm². IP40 enclosure protection, IK07 impact rating.

Selectivity and coordination context

The neutral is on the left; auxiliary contact presence is signalled by a green flag on the front.

MPN
C11H44V025L