Skip to main content
Schneider Electric C11N44V025L

Schneider Electric C11N44V025L ComPacT NSXm MCCB, 25 A, 50 k

MPN C11N44V025L
Active

Schneider Electric ComPacT NSXm, 4P MCCB, 25 A at 40 °C, 50 kA at 415 V AC, electronic trip unit MicroLogic 4.1, integrated earth-leakage protection, grey (RAL 7016).

$793.84 – $835.65 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C11N44V025L key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm with spreaders 27 mm without spreaders
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C

All specifications

C11N44V025L additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
ColorGrey (RAL 7016)
Depth80 mm
Width108 mm
Height144 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Safety categoryN 50 kA 415 V AC
Operating temperature-25...70 °C

Product details

The Schneider Electric C11N44V025L is a ComPacT NSXm 63N frame moulded-case circuit breaker, 4-pole, with a MicroLogic 4.1 electronic trip unit rated 25 A at 40 °C. The integrated earth-leakage protection covers Class A and Class AC sensitivities from 30 mA to 5 A, so it handles both personnel protection and equipment ground-fault detection in one device.

The front-facing Everlink lugs accept 2.5–70 mm² fine-stranded copper or 2.5–95 mm² rigid copper/aluminium, which covers most panel feed and distribution wiring without adapters. At 80 mm deep and 108 mm wide, it occupies 12 module pitches on a 9 mm grid — a compact footprint for a 4-pole 50 kA breaker with integrated earth leakage.

IP40 front panel, IK07 impact resistance. Electrical endurance is 20,000 cycles at rated current, 10,000 at 2× In; mechanical endurance 20,000 cycles. The electronic trip unit includes a 20-minute thermal memory that retains the thermal state before and after a trip, preventing nuisance re-closure on a hot conductor.

MPN