Skip to main content
Schneider Electric C12B34V160B

Schneider Electric C12B34V160B ComPacT NSXm MCCB, 160 A, 25

MPN C12B34V160B
Active

Schneider Electric ComPacT NSXm, C12B34V160B, 3P MCCB, 160 A at 40 °C, B 25 kA 415 V AC, MicroLogic 4.1 electronic trip unit with integrated earth-leakage protection, IP40, grey (RAL 7016).

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C12B34V160B key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm with spreaders 27 mm without spreaders
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C

All specifications

C12B34V160B additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
ColorGrey (RAL 7016)
Depth80 mm
Width108 mm
Height144 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Safety categoryB 25 kA 415 V AC
Operating temperature-25...70 °C

Product details

The Schneider Electric C12B34V160B is a ComPacT NSXm moulded-case circuit breaker (MCCB) — 3-pole, 160 A frame rated at 40 °C, with a B performance level giving 25 kA interrupting capacity at 415 V AC. That B rating means it's sized for distribution duty (Category A utilisation) where the fault current is known and coordinated downstream, not for high-stress motor-start or generator protection. The MicroLogic 4.1 electronic trip unit handles the curve; it's the same trip platform used across the NSXm family, so settings and accessories are consistent if you're standardising on this line.

That's the thermal benchmark — if your panel ambient runs hotter, you derate per the manufacturer's curve. Integrated earth-leakage protection is built in, not an add-on module. Sensitivity is selectable: 30 mA, 100 mA, 300 mA, 500 mA, 1 A, 3 A, and 5 A, for both Class A and Class AC detection. IK07 impact resistance handles light mechanical knocks during installation.

Mounts flat on a backplate, horizontally or vertically. The 9-module width at 108 mm and 144 mm height with 80 mm depth fits standard distribution board cutouts. Connection pitch: 35 mm with spreaders, 27 mm without. Both line and load connections are front-accessed — compression lugs or busbars. That front-access layout keeps wiring clear of the backpanel and makes swap-out easier in a live panel.

MPN
C12B34V160B