Schneider Electric ComPacT NSXm, C12B34V160B, 3P MCCB, 160 A at 40 °C, B 25 kA 415 V AC, MicroLogic 4.1 electronic trip unit with integrated earth-leakage protection, IP40, grey (RAL 7016).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C12B34V160B — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA for class A 100 mA for class A 300 mA for class A 500 mA for class A 1 A for class A 30 mA for class AC 100 mA for class AC 300 mA for class AC 500 mA for class AC 1 A for class AC 3 A for class AC 5 A for class AC
Earth-leakage protection class / typeClass A Class AC
Trip unit technologyElectronic
Local signalling / indicationFlag (green) for presence of auxiliary contacts
C12B34V160B — Electrical Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (operating cycles)20000 cycles
C12B34V160B — Identification
ParameterValue
Product nameComPacT NSXm
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSXm 160B
C12B34V160B — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
Width in 9 mm modules9 module
C12B34V160B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude2000 m without derating 5000 m with derating
C12B34V160B — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The Schneider Electric C12B34V160B is a ComPacT NSXm moulded-case circuit breaker (MCCB) — 3-pole, 160 A frame rated at 40 °C, with a B performance level giving 25 kA interrupting capacity at 415 V AC. That B rating means it's sized for distribution duty (Category A utilisation) where the fault current is known and coordinated downstream, not for high-stress motor-start or generator protection. The MicroLogic 4.1 electronic trip unit handles the curve; it's the same trip platform used across the NSXm family, so settings and accessories are consistent if you're standardising on this line.

That's the thermal benchmark — if your panel ambient runs hotter, you derate per the manufacturer's curve. Integrated earth-leakage protection is built in, not an add-on module. Sensitivity is selectable: 30 mA, 100 mA, 300 mA, 500 mA, 1 A, 3 A, and 5 A, for both Class A and Class AC detection. IK07 impact resistance handles light mechanical knocks during installation.

Mounts flat on a backplate, horizontally or vertically. The 9-module width at 108 mm and 144 mm height with 80 mm depth fits standard distribution board cutouts. Connection pitch: 35 mm with spreaders, 27 mm without. Both line and load connections are front-accessed — compression lugs or busbars. That front-access layout keeps wiring clear of the backpanel and makes swap-out easier in a live panel.

Frequently asked questions

What is C12B34V160B's interrupting rating?

B performance level: 25 kA at 415 V AC. That's the maximum fault current this 3-pole MCCB can safely interrupt at that voltage.

What trip unit does C12B34V160B use?

MicroLogic 4.1 electronic trip unit with integrated earth-leakage protection. Sensitivity is field-selectable from 30 mA to 5 A for both Class A and Class AC detection.