Skip to main content
Schneider Electric C12H44V160B

Schneider Electric C12H44V160B ComPacT NSXm 160A MCCB, 70kA

MPN C12H44V160B
Active

Schneider Electric ComPacT NSXm, MCCB, 160 A at 40 °C, 4P, 70 kA 415 V AC, MicroLogic 4.1 electronic trip unit, EN/IEC 60947-2, Grey (RAL 7016).

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C12H44V160B key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm with spreaders 27 mm without spreaders
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C

All specifications

C12H44V160B additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
ColorGrey (RAL 7016)
Depth80 mm
Width108 mm
Height144 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Safety categoryH 70 kA 415 V AC
Operating temperature-25...70 °C

Product details

ComPacT NSXm 160H — MCCB with integrated earth-leakage

The Schneider Electric C12H44V160B is a ComPacT NSXm 160H moulded-case circuit breaker rated 160 A at 40 °C, 4 poles, with a MicroLogic 4.1 electronic trip unit. The integrated earth-leakage protection — selectable from 30 mA to 5 A, class A or AC — means this single device covers both overcurrent and ground-fault protection, saving a panel row and a separate RCCB.

Overvoltage category IV means it can be installed at the service entrance, not just downstream.

Front connections top and bottom accept compression lugs or busbars. 12-module pitch (9 mm each) means it occupies 108 mm width in a panel; depth is 80 mm, height 144 mm. Neutral is on the left. The 35 mm connection pitch with spreaders (27 mm without) matches standard busbar drilling patterns. Local signalling flag (green) shows presence of auxiliary contacts — useful during commissioning to confirm the aux contact block is seated.

That matters for motor or transformer feeders where repeated inrush can accumulate heat. Electrical durability is 20,000 cycles at rated current and 440 V, halved to 10,000 cycles at In/2 — fine for a panel main or feeder, not for a switching duty contactor.

MPN
C12H44V160B