Skip to main content
Schneider Electric C160H450FM

Schneider C160H450FM ComPacT NS 1600A, 70kA 415V, MicroLogic

MPN C160H450FM
Active

Schneider Electric ComPacT NS new generation, C160H450FM, fixed-mount 4P circuit breaker, 1600 A at 50 °C, MicroLogic 5.0 electronic trip unit, 70 kA Icu at 415 V AC, IEC 60947-2.

$8,670.19 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C160H450FM key specifications
ParameterValue
Control typeManually operated
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Utilization categoryCategory B
IP ratingIP40
Terminal pitch70 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

C160H450FM additional specifications
ParameterValue
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degree3 conforming to IEC 60947
Depth147 mm
Width280 mm
Height327 mm
Electrical life cycles1000 cycles at 690 V In 2000 cycles at 690 V In/2 2000 cycles at 440 V In 5000 cycles at 440 V In/2
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C160H450FM is a Schneider ComPacT NS new generation 4-pole circuit breaker, rated 1600 A at 50 °C with a MicroLogic 5.0 electronic trip unit. This is the part you spec into a main switchboard or heavy distribution panel where you need L, S, and I protection curves configurable via the trip unit.

Drop to 690 V and it still holds 42 kA Icu, which covers most industrial step-down transformers. The IEC 60947-2 Category B rating means it's fully selective with downstream breakers, so a fault on a branch won't take the whole board dark. For a 1600 A main, that matters.

Trip unit and protection curves

The 20-minute thermal memory means it remembers prior heating after a trip — no nuisance reclose on a still-hot cable. Power losses are 74 W at rated current, which matters for ventilation calc in a sealed enclosure. Four red LEDs for fault type and one yellow for overload give you a quick diagnostic without plugging in a UTA.

Operates at 0–2000 m without derating; above that, up to 5000 m with derating. Humidity tolerance 0–95% non-condensing. Complies with EN/IEC 60947-2; no earth-leakage protection built in (that's a separate module).

Durability and service life

Mechanical durability is 10,000 cycles — the handle mechanism. Electrical durability depends on the load: 1000 cycles at full 690 V In, 2000 at half load, 5000 at 440 V full load, and 5000 at half load. That's typical for a fixed-mount breaker of this class; it's not a switching device for daily motor starts, but it handles infrequent manual operations and maintenance switching without issue.