Skip to main content
Schneider Electric C16H34V160

Schneider C16H34V160 ComPacT NSX160H MCCB, 160 A, 70 kA

MPN C16H34V160
Active

Schneider Electric ComPacT NSX series, C16H34V160 NSX160H earth leakage circuit breaker, 3P, 160 A, MicroLogic 4.2 electronic trip unit, 70 kA at 415 V AC.

$1,125.64 – $2,569.32 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C16H34V160 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C16H34V160 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical life cycles40000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C16H34V160: The H breaking capacity code delivers 70 kA Icu at 380/415 V AC, 65 kA at 440 V, and 100 kA at 220/240 V, all per IEC 60947-2. At 480 V AC the breaker is also rated 65 kA Icu per UL 60947-4-1. This level of interrupting capacity allows the NSX160H to be used as a main or feeder breaker in high-fault installations where downstream coordination with lower-rated devices is required. The 160 A frame size with H rating is a common choice for distribution panels feeding motor control centers or large branch circuits.

Trip unit and protection logic

The MicroLogic 4.2 electronic trip unit is field-adjustable for long-time pickup and delay, short-time fixed delay, and instantaneous pickup. Earth-leakage protection is integrated, with sensitivity set via the IΔn rotary switch. Local signaling uses a flashing green LED for ready-to-operate status, a red LED at 105 % Ir for overload, and an orange LED at 90 % Ir for pre-alarm.

Mounting and environmental ratings

The IP40 enclosure (IK07 impact resistance) suits indoor panel installation in dry environments. Operating altitude is 0–2000 m without derating, with derating required above 2000 m.

MPN
C16H34V160